Publication 2711-UM014B-EN-P
Applying Power and Resetting Terminal 2-7
Resetting the Terminal
Resetting the terminal re-initializes the PanelView terminal (same as
cycling power).
To reset the PV300, PV300 Micro, PV550 (keypad, keypad &
touch) or the PV600 (keypad, keypad & touch):
• Simultaneously press the Left arrow , Right arrow , and Enter
↵ keys. The terminal performs its powerup sequence.
The sequence in which keys are pressed (while running an
application), determines what appears after the reset.
• If you press the Left and Right arrow keys before the Enter
↵ key, the Configuration Mode menu appears.
• If you press the Enter ↵ key before the arrow keys, the terminal
runs the loaded application.
To reset the PV550 & PV600 (touch only)/PV900/PV1000/
PV1400:
1. Use a narrow non-conductive tool to press the reset button
shown below. The terminal performs its powerup sequence.
TIP
If the Left or Right arrow keys on the PanelView
300 Micro are assigned as function keys, you must
use the GoTo Configuration Screen button.
ATTENTION
!
Use a nonconducting object to press the Reset
button. Do not use a conducting object such
as a paper clip which may damage the
terminal. Do not use the tip of a pencil,
graphite may damage the terminal.
On the PV550/PV600 touch screen terminals,
the Reset button is located on the right, below the Memory Card slot.
Reset Button
PanelView 1400
PanelView 900/1000