PE6108AV / PE6208AV / PE8208AV User Manual
34
Configuration (PE6208AV)
The Configuration page is used to configure the settings of the PE6208AV at
the individual power outlet level.
POP Settings
This section allows you to enable Proactive Overload Protection (POP).
Proactive Overload Protection is triggered when the PDU’s Aggregate
Current Max Threshold setting is exceeded (see page 31). Effective on all
outlets, this added safety feature automatically powers off the outlets
according to the settings below:
Enable Bank POP Priority Mode checking this box enables
Proactive Overload Protection and will power off outlets according to
the Bank POP Priority List (see page 35).
Power On Time Schedule Settings
Check the Enable Power On Time Schedule box to use the Power ON
Delay setting to set the amount of time the eco PDU waits before powering
on an outlet. See Power ON Delay in the table on the next page.
Buzzer Setting
Checking the Enable Buzzer Alarm box sounds an alarm and sends
SNMP trap or e-mail alerts when a threshold setting exceeds the minimum
or maximum setting.
Outlet Reboot Setting
Checking the Enable Outlet Sequential Reboot box allows you to
sequentially reboot all outlets by pressing the Power Control Button of
Outlet 1 for more than 8 seconds.

Table of Contents