EasyManuals Logo

ATEN PE6108AV User Manual

ATEN PE6108AV
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
PE6108AV / PE6208AV / PE8208AV User Manual
36
Configuration (PE8208AV)
The Configuration page is used to configure the settings of the PE8208AV at
the individual power outlet level:
POP Settings
This section allows you to enable Proactive Overload Protection (POP).
Proactive Overload Protection is triggered when a PDU’s or Outlet’s
Current Max Threshold setting is exceeded. Effective on all outlets, this
added safety feature automatically powers off outlets according to the
settings below:
Enable Outlet POP checking this box triggers Proactive Overload
Protection to power off an outlet when it’s Current Max Threshold
setting is exceeded (see page 33).
Enable Bank POP LIFO Mode checking this box triggers Proactive
Overload Protection to power off a newly inserted device (LIFO),
when it causes the PDU’s Aggregate Current Max Threshold setting to
be exceeded (see page 31). All other outlets stay powered on.
Enable Bank POP Priority Mode checking this box triggers
Proactive Overload Protection when the PDU’s Aggregate Current
Max Threshold setting is exceeded (see page 31). This will power off
outlets according to the Bank POP Priority List settings (see page 37).
For more information about how the POP Settings work together, see
POP Setting Scenarios, page 38.