Product overview
BC315012 Version: 2.1.0
2.3.2 Technical data - PROFIBUS-DP
Fig.2: BC3150
System data PROFIBUS (BC3150)
Number of I/O modules 126 (BC3150 max. 99 devices)
Number of I/O points depending on controller
Data transfer medium shielded copper cable 2 x 0.25mm², cable type A according to
EN50170
Segment length up to 1200m
Number of segments 3
Data transfer rate up to 12MBaud
Topology RS485 line, optical fiber ring
Transmission time approx. 0.5ms with 10 stations for 32bits input/output at 12MBaud
2.3.3 Technical Data - PLC
PLC data BCxx5x
Programmability via serial programming interface or via the fieldbus
Program memory 48kbyte
Source code memory 128kbyte
Data memory 32kbyte
Remanent flags 2kbyte
PLC cycle time Approx. 3.0ms for 1000 IL commands (without I/O cycle)
Programming languages IEC 6-1131-3 (IL, LD, FBD, ST, SFC)
Runtime 1 PLC task
Online Change Yes
Up/Down Load Code Yes/Yes