Parameterization and Commissioning
BC3150 39Version: 2.1.0
Fig.32: Inserting BX3100
Inserting the BX3100 in a PROFIBUS master via the System Manager
Select your PROFIBUS master PC card in the System Manager and right-click on your PROFIBUS master
card. The PROFIBUS devices will then be offered for selection, among them a BX3100. Select this and
confirm with OK.
Opening an existing BX file
If you wish to work with the DEFAULT-CONFIG, interrupt the process at this point (see Creating PROFIBUS
data in DEFAULT-CONFIG). Otherwise select your configured BX file. If no such file exists, you have to
create one (Creating a BX file [}29]). Once you have selected your BX file, all required PROFIBUS data are
copied automatically into your project from this file. You now have to create a link to your task and set the
PROFIBUS address. The configuration can then be saved and the TwinCAT system started.
Creating PROFIBUS data in DEFAULT-CONFIG
• The PROFIBUS data can now be created. Various variables are available:
◦ Integer 8bit
◦ Integer 16bit
◦ Integer 32bit
◦ Unsigned 8bit
◦ Unsigned 16bit
◦ Unsigned 32bit
◦ FLOAT 32bit
They have to match the variable types currently projected in the BX.
Data sizes from 1byte to 64words are available.