Parameterization and Commissioning
BC315038 Version: 2.1.0
4.2.7.2 Master configuration
4.2.7.2.1 Basic Device File (GSD)
All field devices with PROFIBUS slave interface are described via the GSD file. The BX3100 is a PROFIBUS
DP slave. For data exchange, the GSD file has to be inserted in the master configuration tool. The maximum
length of input and output data 244 bytes in each direction.
Download GSD file (German) (https://infosys.beckhoff.com/content/1033/bc3150/Resources/
zip/3238674315.zip)
Download GSD file (English) (https://infosys.beckhoff.com/content/1033/bc3150/Resources/
zip/3238672139.zip)
These files are also available from the Beckhoff website: http://www.beckhoff.de/german/download/
bkconfg.htm
The GSD file can describe the following data types:
Variable Length
Integer 8 1bytes
UnInteger 8 1bytes
Integer 16 2bytes
UnInteger 16 2bytes
Integer 32 4bytes
UnInteger 32 4bytes
Float 32 4bytes
Data types that are not listed, e.g. BOOL variables, can be described via the length. For this purpose, the
GSD file includes configuration data starting with a byte and ending with 64 words.
4.2.7.2.2 Creating a TwinCAT PC file
DEFAULT CONFIG
DEFAULT-CONFIG contains the PROFIBUS data from the address %IB1000 input and %QB1000. The data
length depends on the number of configured PROFIBUS data. A maximum of 244bytes of input data and
244bytes of output data can be parameterized. No further settings are required for this configuration type.