EasyManuals Logo
Home>Beckhoff>Controller>BC3150

Beckhoff BC3150 User Manual

Beckhoff BC3150
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
Error handling and diagnosis
BC315090 Version: 2.1.0
K-Bus error code diagnostics
Error
code
Error
argument
Description Remedy
0 - EMC problems Check power supply for undervoltage or
overvoltage peaks
Implement EMC measures
If a K-bus error is present, it can be localized
by a restart of the coupler (by switching it off
and then on again)
1 0 EEPROM checksum error Enter factory settings with the KS2000 configuration
software
1 Code buffer overflow Insert fewer Bus Terminals. Too many entries in the
table for the programmed configuration
2 Unknown data type Software update required for the Bus Coupler
2 - Reserve -
3 0 K-bus command error No Bus Terminal inserted
One of the Bus Terminals is defective; halve
the number of Bus Terminals attached and
check whether the error is still present with
the remaining Bus Terminals. Repeat until the
defective Bus Terminal is located.
4 0 K-bus data error, break behind
the Bus Coupler
Check whether the n+1 Bus Terminal is correctly
connected; replace if necessary.
n Break behind Bus Terminaln Check whether the KL9010 Bus End Terminal is
connected
5 n K-bus error in register
communication with Bus
Terminal n
Exchange the nth Bus Terminal
6 0 Error at initialization Exchange Bus Coupler
1 Internal data error Perform a hardware reset on the Bus Coupler
(switch off and on again)
2 DIP switch changed after a
software reset
Perform a hardware reset on the Bus Coupler
(switch off and on again)
7 0 Note: cycle time was exceeded Warning: the set cycle time was exceeded. This
indication (flashing LEDs) can only be cleared by
booting the Bus Coupler again.
Remedy: increase the cycle time
9 0 Checksum error in Flash
program
Re-transfer the program to the Bus Terminal
Controller
1 Incorrect or faulty library
implemented
Remove the faulty library
10 n Bus Terminal n is not
consistent with the
configuration that existed when
the boot project was created
Check the nth Bus Terminal. The boot project must
be deleted if the insertion of an nth Bus Terminal is
intentional.
14 n nth Bus Terminal has the wrong
format
Start the Bus Coupler again, and if the error occurs
again then exchange the Bus Terminal
15 n Number of Bus Terminals is no
longer correct
Start the Bus Coupler again. If the error occurs
again, restore the manufacturers setting using the
KS2000 configuration software
16 n Length of the K-bus data is no
longer correct
Start the Bus Coupler again. If the error occurs
again, restore the manufacturers setting using the
KS2000 configuration software

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff BC3150 and is the answer not in the manual?

Beckhoff BC3150 Specifications

General IconGeneral
BrandBeckhoff
ModelBC3150
CategoryController
LanguageEnglish