EasyManuals Logo

Carrier Aquasnap 30RQ User Manual

Carrier Aquasnap 30RQ
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
4.3 - Free spaces
The free spaces presented are determined in order to ensure
su󰀩cient working and manoeuvring space to carry out maintenance 
operations on the unit in suitable ergonomic conditions
2523 HT
1500
2200
1500
1500
B
B
B
B C
Key:
All dimensions are given in mm.
B
Clearances required for maintenance and air ow
C
Clearance recommended for coil removal
4.4 - Positioning of potentially ammable zones
around the unit
Electrical cabinet side
60cm
The complete unit, including all the options and accessories which
are provided by the manufacturer, have been certied for use with 
an A2L refrigerant.
To ensure this, the manufacturer complies with EN 378-2 §6.2.14
and has dened a potentially ammable zone using EN 60079-
10-1 in order to identify where no sources of ignition must be
present.
The manufacturer has then designed the machine so that, if the
unit is used in the manner for which it has been designed, there
are  no  internal  sources  of  ignition  in  the  potentially  ammable 
zone inside the machine.
Therefore, the only residual risk is that a source of ignition is
introduced into the potentially flammable zone by the user.
This is why the manufacturer has decided to show the potentially
ammable  zone  around  the  machine  (see  the  diagram  above) 
into which the user must not introduce any sources of ignition.
This indication is only provided to help our customers to identify
the limits of the ammability risk.
However, the machine itself does not present any risk of explosion
connected to the use of A2L refrigerant.
Note (the following information is provided by the manufacturer 
for guidance only. The application of the following directives is the
sole responsibility of the user):
In compliance with the directives 2009/104/EC and 1999/92/EC,
these zones may be qualied as ATEX zones by the user on the 
basis of their own risk analysis, for which they alone remain
responsible. In accordance with the denition given by Annex I of 
the directive 1999/92/EC, this zone may be classied as zone 2 
since it may consist of a location where an explosive atmosphere
consisting of  a mixture  of air  and ammable substances in the 
form of a gas is not liable to occur during normal operation or, if
it does occur, it only occurs for a short period of time.
If additional equipment is required (motorised valve, pump, etc.), 
it must be:
Installed outside of the dened potentially ammable zone 
Certied as  not being a source of  ignition for  the refrigerant 
used.
4.5 - Installing several units
It is recommended to install multiple units in a single row, arranged
as shown in the example below, to avoid recycling air between
the units. If the oor space does not allow this arrangement, contact 
your distributor to assess the various installation options.
1500 mm min.
1500 mm
min.
4.6 - Distance to the wall
Plots
Antivibratiles
H
S
h
To guarantee correct operation in most cases:
If h < H, S minimum = 3 m
If h > H or S < 3 m, contact your distributor to assess the various
installation options.
4 - DIMENSIONS, CLEARANCES, MINIMUM INSTALLATION DISTANCES
11

Table of Contents

Other manuals for Carrier Aquasnap 30RQ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Aquasnap 30RQ and is the answer not in the manual?

Carrier Aquasnap 30RQ Specifications

General IconGeneral
BrandCarrier
ModelAquasnap 30RQ
CategoryChiller
LanguageEnglish

Related product manuals