Procedure for controlling the pressure di󰀨erential setpoint
Once the circuit is cleaned, place the hydraulic circuit in the
conguration for which the unit selection was performed (generally, 
this will be all valves open and all cooling coils active)
Read the ow rate on the user interface and compare the value 
obtained with the theoretical value of the selection:
If the ow rate read is greater than the preset value, reduce the 
pressure di󰀨erential setpoint on the user interface to reduce 
the ow rate value;
If the ow rate read is lower than the preset value, increase the 
pressure di󰀨erential setpoint on the user interface to increase 
the ow rate value
Repeat until the unit's nominal ow rate at the required operation 
point is achieved.
Stop the forced operation of the pump and proceed to the
conguration of the unit for the required control mode. Modify the 
control parameters:
Set the water ow rate control to “pressure di󰀨erential”
Set the value of the required pressure di󰀨erential.
The  unit's  default  factory  conguration  is  the  minimum  speed 
(frequency: 30 Hz).
NOTE:
If during adjustment, the low or high frequency limits are
reached before reaching the specied ow rate, keep the
pressure di󰀨erential value at its lower or higher limit as the
control parameter value.
If the user knows in advance the pressure di󰀨erential value
at the unit outlet to be maintained, this value can be entered
directly as a parameter to be declared. You should not,
however, omit the hydraulic circuit cleaning sequence
9.4 - Units with hydraulic module and variable-
speed pump – Temperature di󰀨erential control
The installation ow rate has not been set to a rated value.
The  ow  rate  will  be  adjusted,  by  varying  the  pump  speed, 
to maintain a heat exchanger temperature di󰀨erential value dened 
by the user.
This is checked by the temperature sensors at the water exchanger
inlet  and  outlet  (items  8  and  9  on  the  typical  hydraulic  circuit 
diagram).
The system reads the measured temperature values, calculates
the corresponding Delta T°, compares it with the setpoint value
set by the user and then modulates the pump speed accordingly.
This results in an increase in the ow rate if the Delta T° exceeds 
the setpoint.
This results in a decrease in the ow rate if the Delta T° is less 
than the setpoint.
This variation in ow rate is limited by the maximum and minimum 
permissible ow rate values for the unit and by the maximum and 
minimum pump supply frequency values.
The  maintained  Delta  T°  may,  in  certain  cases,  di󰀨er  from  the 
setpoint value:
If the setpoint value is too high (corresponding to a ow rate 
lower than the minimum value or a frequency less than the
minimum value), the system will be limited to the minimum ow 
rate or minimum frequency, which will result in a
Delta T below the setpoint,
If the setpoint  value is too low (corresponding to a ow rate 
higher than the maximum value or a frequency greater than
the maximum value), the system will be limited to the maximum 
ow rate or maximum frequency, which will result in a Delta T 
above the setpoint.
Contact the manufacturer's Service to implement the procedures
described below.
Hydraulic circuit cleaning procedure
Refer to the hydraulic circuit cleaning procedure.
Procedure for adjusting the Delta T° setpoint
Once the circuit is cleaned, stop the forced start of the pump and
proceed to the conguration of  the unit for the required  control 
mode.
Modify the control parameters:
Water ow rate control method (temperature di󰀨erential)
Set the required Delta T.
The  unit's  default  factory  conguration  is  the  minimum  speed 
(frequency: 30 Hz).
9.5 - Units with hydraulic module and variable-
speed pump - Setting a xed ow rate for the
system
The ow will be set to a nominal value.  This  value  will  remain 
constant, and will not be dependent on variations in the
installation's load.
Contact the manufacturer's service department to implement the
procedures described below
Hydraulic circuit cleaning procedure
Refer to the hydraulic circuit cleaning procedure.
Procedure for controlling the ow rate
Once the circuit has been  cleaned, set the required water  ow 
rate by adjusting the pump frequency on the user interface.
Stop the forced operation of the pump and proceed to
the conguration of the unit for the required control mode. Modify 
the control parameters:
Water ow rate control method (xed speed)
Constant frequency value.
The  unit's  default  factory  conguration  is  the  minimum  speed 
(frequency: 30 Hz).
9 - NOMINAL SYSTEM WATER FLOW RATE CONTROL
50

Table of Contents

Other manuals for Carrier Aquasnap 30RQ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Aquasnap 30RQ and is the answer not in the manual?

Carrier Aquasnap 30RQ Specifications

General IconGeneral
BrandCarrier
ModelAquasnap 30RQ
CategoryChiller
LanguageEnglish

Related product manuals