EasyManuals Logo

Carrier Aquasnap 30RQ User Manual

Carrier Aquasnap 30RQ
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
Water ow rate adjustment procedure
Once the circuit is cleaned, read the ow rate value on the user 
interface and compare it to the theoretical selection value.
If the value of the ow rate read is greater than the specied value,
this indicates that the overall pressure drop in the system is too
low compared to the available static pressure generated by the
pump.
In this case, close the control valve (item 22) and read the new 
ow rate value.
Proceed by repeatedly closing the control valve (item 22) until the 
nominal ow rate is achieved at the unit's required operation point.
NOTE:
If the network has an excessive pressure drop in relation to
the available static pressure delivered by the unit pump, the
nominal water ow rate cannot be obtained (lower resulting
ow rate) and the di󰀨erence in temperature between the water
inlet and outlet of the water type heat exchanger will be
increased
To reduce the installation's hydraulic system pressure drop, it is
necessary to:
Reduce the pressure drops of individual components (bends, 
level changes, options, etc.) as much as possible;
Use the correct pipe diameter;
Do not extend the hydraulic systems
Example: Unit with specied
nominal ow rate of 10.6 l/s
Pressure drop, kPa
Water ow rate, l/s
B
C
D
E
Key
B
Unit pump curve
C
Pressure drop in the hydraulic module (to be measured on the pressure gauge 
installed on the water inlet and outlet)
D
Pressure drop in the installation with wide open control valve
E
Pressure drop in the system after setting the valve to obtain the nominal ow 
rate specied.
9.3 - Units with hydraulic module and variable-
speed pump – Pressure di󰀨erential control
The installation ow rate has not been set to a rated value.
It will be adjusted by the system, by varying the pump speed,
to maintain a constant operating pressure di󰀨erential value dened 
by the user.
This is checked by the pressure sensor at the outlet of the water
type  heat  exchanger  (item  10  on  the  typical  hydraulic  circuit 
diagram).
The system calculates the measured pressure difference,
compares it with the setpoint value set by the user and then
modulates the pump speed module accordingly, resulting in:
An increase in the ow rate if the measurement is below the 
setpoint,
Adecrease in the ow rate if the measurement exceeds the 
setpoint.
This variation in ow rate is limited by the maximum and minimum 
permissible ow rate values for the unit and by the maximum and 
minimum pump supply frequency values.
The maintained pressure di󰀨erence value may, in certain cases, 
di󰀨er from the setpoint value:
If the setpoint value is too high (obtained for a ow rate higher 
than the maximum value or a frequency greater than the
maximum  value),  the  system  will  stop  once  it  reaches  the 
maximum ow rate or maximum frequency, which will result in 
a pressure di󰀨erence below the setpoint,
If the setpoint value is too low (obtained for a ow rate lower 
than the minimum value or a frequency less than the minimum
value), the system will stop once it reaches the minimum ow 
rate or minimum frequency, which will result in a pressure
di󰀨erence greater than the setpoint.
Contact the manufacturer's Service to implement the procedures
described below
Hydraulic circuit cleaning procedure
Before proceeding, it is advisable to remove any possible
contamination from the hydraulic circuit.
Start up the unit pump using the override command.
Set the frequency to the maximum value to generate a high
ow rate.
If  there  is  a  “Maximum  ow  exceeded”  alarm,  reduce  the 
frequency until an acceptable value is reached.
Read the ow rate on the user interface.
Let the pump run for 2 hours continuously to ush the system's 
hydraulic circuit (presence of contaminating solids).
Perform another reading of the ow rate and compare this value 
with the initial value. Adecrease in the ow rate value indicates 
that the lters in the system need to be removed and cleaned. 
In this case, close the shut-o󰀨 valves on the water inlet and 
outlet (item 19) and remove the lters (items 20 and 1) after 
draining the hydraulic part of the unit (items 6).
Remove the air from the circuit (items 5 and 17).
Repeat until all fouling is removed from the lter
9 - NOMINAL SYSTEM WATER FLOW RATE CONTROL
49

Table of Contents

Other manuals for Carrier Aquasnap 30RQ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Aquasnap 30RQ and is the answer not in the manual?

Carrier Aquasnap 30RQ Specifications

General IconGeneral
BrandCarrier
ModelAquasnap 30RQ
CategoryChiller
LanguageEnglish

Related product manuals