Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
79
Point Name/Description
Range
Compressor Stages
The number of mechanical cooling stages.
Not displayed if
Unit Type
is set to
LC WeatherExpert
™.
D:
R:
One Stage
One Stage
Two Stages
Face Split Coil
Applies only to 2-stage cooling unit with variable speed fan control, this
defines the type of cooling coil installed in the unit. The controller uses it to estimate
the temperature of the air leaving the active portion of the cooling coil during part-load
operation.
Not displayed if
Unit Type
is set to
LC WeatherExpert
™.
D:
R:
Yes
No/Yes
Economizer Exists
Set to
Yes
to enable economizer control for units equipped with an
economizer damper.
D:
R:
No
No/Yes
Fan Control
The type of fan control used on this unit.
Automatically set to
Variable Speed
if
Unit Type
is set to
LC WeatherExpert
™.
D:
R:
Single Speed
Single Speed
Two Speed
Variable Speed
VFD Input
Defines the electrical control signal used by the Variable Frequency Drive’s
(VFD) input. Applies to
Variable Speed
fan control only.
D:
R:
2-10 Vdc
0-10 Vdc
2-10 Vdc
Max VFD Output
The maximum output signal the control supplies to the VFD as a
percentage of its range. The balancer can set this to adjust the unit’s maximum airflow.
Applies to
Variable Speed
fan control only.
D:
R:
100%
33% to 100%
Min VFD Output
The minimum output signal the control supplies to the VFD as a
percentage of its range. The balancer can set this to adjust the unit’s minimum airflow.
Applies to
Variable Speed
fan control only.
D:
R:
40%
33% to 100%
Dehum Min VFD Output
The minimum output signal supplied by the control during
dehumidification as a percentage of its range. Applies only to
Variable Speed
fan
control.
D:
R:
60%
50% to 100%
Stage 1 SAT Stpt
The VFD Supply Air Setpoint during stage 1 cooling.
Must be at least 4°F (2.2°C) greater than
Minimum Cooling SAT
.
D:
R:
57°F (13.9°C)
45 to 75°F
(7.2 to 23.9°C)
Stage 2 SAT Stpt
The VFD Supply Air Setpoint during stage 2 cooling.
Must be at least 4°F (2.2°C) greater than
Minimum Cooling SAT
.
D:
R:
57°F (13.9°C)
45 to 75°F
(7.2 to 23.9°C)
Stage 3 SAT Stpt
The VFD Supply Air Setpoint during stage 3 cooling.
Must be at least 4°F (2.2°C) greater than
Minimum Cooling SAT
.
D:
R:
56°F (13.3°C)
45 to 75°F
(7.2 to 23.9°C)
Reversing Valve Output
The type of reversing valve this unit uses. D:
R:
O
O/B
Heat Type
The type of heating used by the unit.
D:
R:
Electric
Electric/Gas
Number of Heat Stages
The number heat stages. D:
R:
2
1 / 2 /0 (no heating)

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals