Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
79
– The number of mechanical cooling stages.
Not displayed if
is set to
™.
D:
R:
One Stage
One Stage
Two Stages
– Applies only to 2-stage cooling unit with variable speed fan control, this
defines the type of cooling coil installed in the unit. The controller uses it to estimate
the temperature of the air leaving the active portion of the cooling coil during part-load
operation.
Not displayed if
is set to
™.
D:
R:
Yes
No/Yes
– Set to
to enable economizer control for units equipped with an
economizer damper.
D:
R:
No
No/Yes
– The type of fan control used on this unit.
Automatically set to
if
is set to
™.
D:
R:
Single Speed
Single Speed
Two Speed
Variable Speed
– Defines the electrical control signal used by the Variable Frequency Drive’s
(VFD) input. Applies to
fan control only.
D:
R:
2-10 Vdc
0-10 Vdc
2-10 Vdc
– The maximum output signal the control supplies to the VFD as a
percentage of its range. The balancer can set this to adjust the unit’s maximum airflow.
Applies to
fan control only.
D:
R:
100%
33% to 100%
– The minimum output signal the control supplies to the VFD as a
percentage of its range. The balancer can set this to adjust the unit’s minimum airflow.
Applies to
fan control only.
D:
R:
40%
33% to 100%
The minimum output signal supplied by the control during
dehumidification as a percentage of its range. Applies only to
fan
control.
D:
R:
60%
50% to 100%
– The VFD Supply Air Setpoint during stage 1 cooling.
Must be at least 4°F (2.2°C) greater than
.
D:
R:
57°F (13.9°C)
45 to 75°F
(7.2 to 23.9°C)
– The VFD Supply Air Setpoint during stage 2 cooling.
Must be at least 4°F (2.2°C) greater than
.
D:
R:
57°F (13.9°C)
45 to 75°F
(7.2 to 23.9°C)
– The VFD Supply Air Setpoint during stage 3 cooling.
Must be at least 4°F (2.2°C) greater than
.
D:
R:
56°F (13.3°C)
45 to 75°F
(7.2 to 23.9°C)
– The type of reversing valve this unit uses. D:
R:
O
O/B
– The type of heating used by the unit.
D:
R:
Electric
Electric/Gas
– The number heat stages. D:
R:
2
1 / 2 /0 (no heating)