Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
80
Point Name/Description
Range
Continuous Occupied Exhaust
Configures the exhaust fan control strategy (BO-8). If
Yes
, the power exhaust runs continuously in occupied mode and is off in unoccupied
mode. If
No
, the power exhaust is controlled by the
Power Exhaust Setpoint.
D:
R:
No
No/Yes
RH Control
Enables dehumidification control if an RH sensor or humidistat is
available and the unit has the Humidi-MiZer™ dehumidification option installed.
D:
R:
Disable
Disable/Enable
DCV Control
Enables demand controlled ventilation (DCV) if valid CO
2
sensor value is
available and the unit has an economizer installed.
D:
R:
Disable
Disable/Enable
Indoor CO2 Sensor Value @ Min mA
The CO
2
value that corresponds to a 4 mA input
at the appropriate input channel.
D:
R:
0 ppm
0 to 9999 ppm
Indoor CO2 Sensor Value @ Max mA
The CO
2
value that corresponds to a 20 mA
input at the appropriate input channel.
D:
R:
2000 ppm
0 to 9999 ppm
Outdoor CO2 Sensor Value @ Min mA
The CO
2
value that corresponds to a 4 mA input
at the appropriate input channel.
D:
R:
0 ppm
0 to 9999 ppm
Outdoor CO2 Sensor Value @ Max mA
The CO
2
value that corresponds to a 20 mA
input at the appropriate input channel.
D:
R:
2000 ppm
0 to 9999 ppm
System Space Temperature
The network space temperature value that the controller
is using for control (if applicable).
D:
R:
-999.00°
N/A
System Space RH
The network relative humidity value that the controller is using for
control (if applicable).
D:
R:
-999.00%
N/A
System Space AQ
The network indoor air quality (CO
2
) value that the controller is
using for control (if applicable).
D:
R:
-999.00 ppm
N/A
System Cool Demand Level
The system cool demand level being received over the
network.
D:
R:
0.00
0 to 3
System Heat Demand Level
The system heat demand level being received over the
network.
D:
R:
0.00
0 to 3
System Outdoor Air Temperature
Allows the outdoor air temperature value to be
network readable when enabled. Requires controller be equipped with an outdoor air
temperature sensor.
D:
R:
-999.00 ppm
N/A
System Outdoor AQ
Allows network-readable OAQ value for calculating the differential
OAQ CO2 levels and IAQ CO2 levels to drive the IAQ control.
D:
R:
-999.0°
N/A
System Fire / Smoke
Allows network-readable Fire / Smoke signal to force shutdown. D:
R:
Off
Off/On
Service Test

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals