Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
81
Point Name/Description
Default/Range
Service Test
Enable to stop automatic control so you can test the controller's outputs.
Automatically resets to
Disable
after 1 hour.
D:
R:
Disable
Disable/Enable
Fan Test
Enable to test the controller's fan operation. Operates fan at low speed if the
fan type is set to Two Speed. Resets to
Disable
when complete.
Service Test
must be
set to
Enable
.
D:
R:
Disable
Disable/Enable
High Fan Speed Test
Enable to test the unit’s high speed fan operation. Operates fan
at high speed if
Fan Control
is set to
Two Speed
. Resets to
Disable
when complete.
Service Test
must be set to
Enable
.
D:
R:
Disable
Disable/Enable
Compressor 1 Test
Enable to test the controller's compressor 1 output.
Service Test
must be set to
Enable
.
D:
R:
Disable
Disable/Enable
Compressor 2 Test
Enable to test the controller's compressor 2 output.
Service Test
must be set to
Enable
.
D:
R:
Disable
Disable/Enable
Heat 1 Test
Enable to test the controller's heat 1 output.
Service Test
must be set to
Enable
.
D:
R:
Disable
Disable/Enable
Heat 2 Test
Enable to test the controller's heat 2 output.
Service Test
must be set to
Enable
.
D:
R:
Disable
Disable/Enable
Reversing Valve Test
Enable to test the controller's reversing valve output.
Service
Test
must be set to
Enable
.
D:
R:
Disable
Disable/Enable
Dehumidification Test
Enable to test the controller's Humidi-MiZer™ output.
Service
Test
must be set to
Enable
.
D:
R:
Disable
Disable/Enable
Power Exhaust Test
Enable to test the controller's exhaust fan output.
Service Test
must be set to
Enable
.
D:
R:
Disable
Disable/Enable
Economizer Test
Set to a value between 0 and 100% to test the controller's
economizer output.
Service Test
must be set to
Enable
.
D:
R:
0% Open
0 to 100% Open
VFD Speed Test
Set to a value between 0 and 100% to test the controller's variable
speed fan output.
Service Test
must be set to
Enable
.
D:
R:
0%
0 to 100%

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals