Installation 2-11
5150 Service Aggregation Switch Hardware Installation and Start-up Manual
009-3222-001 Standard Revision H
Copyright
©
2012-2015 Ciena
®
Corporation July 2015
Cable Installation and Guidelines
This guide assumes that the site's data cables have been properly installed in
a centrally wired distribution configuration. When installing fiber optic cables
and other network cabling, always have them installed and tested by a
technician who is certified by the Electronics Industry Association/
Telecommunications Industry Association (EIA/TIA). This ensures a quality
installation and presents one less variable to consider when troubleshooting.
When installing cable, Do:
Use more cable than required, leaving some slack.
Test each section of the network as it is installed. Even in new installations,
problems may occur that will be difficult to isolate later.
When using shielded cables, ensure that the cable is terminated to
Ground at both ends
Cover cables with cable protectors if it is necessary to run cables across
the floor.
Label both ends of all cables.
Use cable ties or Velcro tie wraps to secure cables. If staples are used,
they must be hand installed or use a depth stop.
Use cable hangers and J-hooks.
Do NOT:
Use electrical tape or any other type of tape to secure cables.
Over stress cables by over tightening cable ties or stapling cables to the
point where crushing is visible. This is particularly applicable for fiber optic
cables.
Exceed the minimum bending radius for fiber optic cables.
Install cables near sources of electrical interference. All twisted pair wires
must be at least 3 feet away from fluorescent light boxes and other
sources of electrical interference such as a power source. Fiber optic
cables are not affected by electrical interference.
Run cable in power conduits or air plenums.
Note: Fiber optic cables are not affected by electrical interference.
Note: When connecting to copper SFPs, shielded Cat 5e cables are
required. Ensure that both ends of the shielded cable are properly
grounded.
WARNING: All electrical connections are intended for indoor use only.