37
FSM3
Series
IO-Link
Names and functions of display/operation section (IO-Link)
Communication specications
Descriptions Details
Communication protocol IO-Link
Communication protocol version V1.1
Transmission bit rate COM2 (38.4 kbps)
Port Class A
Process data length (input) 4 byte
Process data length (output) 0 byte
Shortest cycle time 5 ms
Data storage 1 kbyte
SIO mode support None
Bit 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Data name
MSB LSB
Instantaneous ow rate
Data range Refer to Table 1
Format Integer 16
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Data name Error
WARNING
- - - -
Switch output
Vacant
2 1
Data range True/False
Format Boolean
Data range (Table 1)
005 010 020 050 100 200 500 101 201 501 102
Data range
(
/min)
[B]
U
0 to
550 mL
0 to
1100 mL
0.00 to
2.20 L
0.00 to
5.50 L
0.00 to
11.00 L
0.0 to
22.0 L
0.0 to
55.0 L
0.0 to
110.0 L
0 to
220 L
0 to
550 L
0 to
1100 L
B
−550 to
550 mL
−1100 to
1100 mL
−2.20 to
2.20 L
−5.50 to
5.50 L
−11.00 to
11.00 L
−22.0 to
22.0 L
−55.0 to
55.0 L
−110.0 to
110.0 L
−220 to
220 L
−550 to
550 L
−1100 to
1100 L
* The data range changes during gas setting for CO
2
. Refer to page 14.
* Download the IO-Link setting le (IODD) from the CKD website (http://www.ckd.co.jp/).
Power lamp (green)
Lights when power supply is ON.
Blinks during IO-Link communication.
Status lamp (green, orange, red)
Green ..... Lights when within specied ow rate range
Orange ...
Lights when ow rate exceeds specied range by less than 10%.
Lights during a warning.
Red ........
Lights when ow rate exceeds specied range by 10% or more.
Lights during an error.
* Lamp turns OFF when the ow rate is 3% (±3%).