3.21 Parameters: 35-** Sensor Input Option
3.21.1 35-0* Temp. Input Mode (MCB 114)
35-00 Term. X48/4 Temp. Unit
Select the unit to be used with temperature input X48/4 settings
and readouts:
Option: Function:
[60]
*
°C
[160] °F
35-01 Term. X48/4 Input Type
View the temperature sensor type detected at input X48/4:
Option: Function:
[0]
*
Not Connected
[1] PT100 2-wire
[3] PT1000 2-wire
[5] PT100 3-wire
[7] PT1000 3-wire
35-02 Term. X48/7 Temp. Unit
Select the unit to be used with temperature input X48/7 settings
and readouts:
Option: Function:
[60]
*
°C
[160] °F
35-03 Term. X48/7 Input Type
View the temperature sensor type detected at input X48/7:
Option: Function:
[0]
*
Not Connected
[1] PT100 2-wire
[3] PT1000 2-wire
[5] PT100 3-wire
[7] PT1000 3-wire
35-04 Term. X48/10 Temp. Unit
Select the unit to be used with temperature input X48/10 settings
and readouts:
Option: Function:
[60]
*
°C
[160] °F
35-05 Term. X48/10 Input Type
View the temperature sensor type detected at input X48/10:
Option: Function:
[0]
*
Not Connected
[1] PT100 2-wire
[3] PT1000 2-wire
[5] PT100 3-wire
[7] PT1000 3-wire
35-06 Temperature Sensor Alarm Function
Select the alarm function:
Option: Function:
[0] Off
[2] Stop
[5]
*
Stop and trip
3.21.2 35-1* Temp. Input X48/4 (MCB 114)
35-14 Term. X48/4 Filter Time Constant
Range: Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/4. A high time constant
value improves dampening but also
increases the time delay through the filter.
35-15 Term. X48/4 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/4. The temperature limits
can be set in par. 35-16 and par. 35-17.
Option: Function:
[0]
*
Disabled
[1] Enabled
35-16 Term. X48/4 Low Temp. Limit
Range: Function:
Application
dependent
*
[Application
dependant]
Enter the minimum
temperature reading that is
expected for normal
operation of the
temperature sensor at
terminal X48/4.
Parameter Descriptions FC 300 Programming Guide
3-144 MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Series and is the answer not in the manual?

Danfoss FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals