[Hand on] - [Off] - [Auto on]
Reset
Coasting stop inverse
Reverse
Set-up select lsb - Set-up select msb
Stop command from serial communication
Quick stop
DC brake
[Off] stops the connected motor. The key can be selected as
Enable [1] or Disable [0] via 0-41 [Off] Key on LCP.
If no external stop function is selected and the [Off] key is
inactive, the motor can be stopped by disconnecting the
voltage.
[Auto on] enables the adjustable frequency drive to be
controlled via the control terminals and/or serial communi-
cation. When a start signal is applied on the control terminals
and/or the bus, the adjustable frequency drive will start. The
key can be selected as Enable [1] or Disable [0] via 0-42 [Auto
on] Key on LCP.
NOTE!
An active HAND-OFF-AUTO signal via the digital inputs has
higher priority than the control keys [Hand on] [Auto on].
[Reset] is used for resetting the adjustable frequency drive
after an alarm (trip). It can be selected as Enable [1] or
Disable [0] via 0-43 [Reset] Key on LCP.
2.1.19 Initialization to Default Settings
Initialize the adjustable frequency drive to default settings in
two ways:
Recommended initialization (via 14-22 Operation Mode)
1. Select 14-22 Operation Mode
2. Press [OK]
3. Select “Initialization”
4. Press [OK]
5. Cut off the line power supply and wait until the display turns
off.
6. Reconnect the line power supply - the adjustable frequency
drive is now reset.
14-22 Operation Mode initializes all except:
14-50 RFI 1
8-30 Protocol
8-31 Address
8-32 FC Port Baud Rate
8-35 Minimum Response Delay
8-36 Max Response Delay
8-37 Max Inter-Char Delay
15-00 Operating Hours to 15-05 Over Volts
15-20 Historic Log: Event to 15-22 Historic Log: Time
15-30 Fault Log: Error Code to 15-32 Alarm Log: Time
Manual initialization
1. Disconnect from the line power and wait until the display
turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time during
power-up for LCP 102, Graphical Display
2b. Press [Menu] while powering up for LCP 101, Numerical
Display
3. Release the keys after 5 s.
4. The adjustable frequency drive is now programmed
according to default settings.
This procedure initializes all except:
15-00 Operating Hours
15-03 Power-ups
15-04 Over Temps
15-05 Over Volts
NOTE!
When you carry out manual initialization, you also reset serial
communication, RFI filter settings (14-50 RFI 1) and fault log
settings.
How to Program FC 300 Programming Guide
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark 2-11
2
2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Series and is the answer not in the manual?

Danfoss FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals