4.1.1 Active/Inactive Parameters in Different
Drive Control Modes
+ = active
- = not active
Par. 1-10 - Motor Construction AC motor PM Non-salient Motor
Par. 1-01 - Motor Control Principle
U/f mode VVC+
Flux open-
loop
Flux closed-
loop
U/f mode
Flux
open-
loop
Flux
closed-
loop
Par. 1-00 - Configuration Mode
[0] Speed Open-loop
+ + + -
[1] Speed Closed-loop - + - +
[2] Torque - - - +
[3] Process + + + -
[4] Torque Open-loop - + - -
[5] Wobble + + + +
[6] Surface Winder + + + -
[7] Ext. PID Open-loop + + + -
[8] Ext. PID Closed-loop - + - +
Par. 1-02 - Flux Motor Feedback Source - - - +
Par. 1-03 - Torque Characteristics
-
+
see 1, 2, 3)
+
see 1, 3, 4)
+
see 1, 3, 4)
Par. 1-04 - Overload Mode + + + + + + +
Par. 1-05 - Local Mode Configuration
+ + + + + + +
Par. 1-06 - Clockwise Direction
+ + + + + + +
Par. 1-20 - Motor Power [KW] (Par. 023 =
International)
+ + + +
Par. 1-21 - Motor Power [HP] (par. 023 =
US)
+ + + +
Par. 1-22 - Motor Voltage + + + +
Par. 1-23 - Motor Frequency + + + +
Par. 1-24 - Motor Current + + + +
Par. 1-25 - Motor Nom. Speed + + + +
Par. 1-26 - Motor Rated Torque - - - - + + +
Par. 1-29 - AMA
+ + + +
Par. 1-30 - RS + + + + +
Par. 1-31 - Rr
-
+
see 5)
+ +
Par. 1-33 - X1 + + + + +
Par. 1-34 - X2
-
+
see 5)
+ +
Par. 1-35 - Xh + + + + +
Par. 1-36 - Rfe - - + + - - -
Par. 1-37 - Ld
- - - - + +
Par. 1-39 - Motor Poles
+ + + +
Par. 1-40 - Back EMF - - - - + + +
Par. 1-41 - Motor Angle Offset
- - - - +
1) Constant torque
2) Variable torque
3) AEO
4) Constant power
5) Used in flystart
Parameter Lists FC 300 Programming Guide
4-2 MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
4