30 MENCODER
MENCODER indicates the number of counts of
the master encoders in pulses counts per revo-
lution.
Content
Resolution of encoder 1 (master)
Parameter Group
AXE
Unit
Encoder counts per revolution
Value range
1 … MLONG ★ 500
31 RAMPMIN
The RAMPMIN parameter determines the shortest
ramp (maximum acceleration). It indicates how
long the acceleration phase lasts at the very least
in order to achieve the rated velocity.
NB!
If you work with the SyncPos option card
then you should always set the ramps via
the option card and not in the VLT. The VLT ramps
must always be set to minimum.
Content
Shortest ramp
Parameter Group
AXV
Unit
msec
Value range
1 … 65535 ★ 1000
32 RAMPTYPE
RAMPTYPE determines the type of ramp used
(trapeze or sinusoidal).
Content
Ramp type
Parameter Group
AXV
Value range
0 – 1 ★ 0
0 = trapeze
1 = sinusoidal
3 3 DFLTVEL
DFLTVEL indicates the default velocity which is
always used when no velocity is defined in the pro-
cess set. This value refers to the
Velocity resolu-Velocity resolu-
Velocity resolu-Velocity resolu-
Velocity resolu-
tion tion
tion tion
tion VELRES (22).
Content
Default velocity
Parameter Group
AXV
Unit
1
/
VELRES;
Standard =
1
/
100
= %
Value range
1 … VELRES ★ 50
Parameter Reference