Illustration 9.4 Recommended Lifting Method for F8 Enclosure
9.3 Operating Environment
In environments with airborne liquids, particles, or
corrosive gases, ensure that the IP/Type rating of the
equipment matches the installation environment. For
specications regarding ambient conditions, see
chapter 7.5 Ambient Conditions.
NOTICE
CONDENSATION
Moisture can condense on the electronic components
and cause short circuits. Avoid installation in areas
subject to frost. Install an optional space heater when
the drive is colder than the ambient air. Operating in
standby mode reduces the risk of condensation as long
as the power dissipation keeps the circuitry free of
moisture.
NOTICE
EXTREME AMBIENT CONDITIONS
Hot or cold temperatures compromise unit performance
and longevity.
Do not operate in environments where the
ambient temperature exceeds 55 °C (131 °F).
The drive can operate at temperatures down to
-10 °C (14 °F). However, proper operation at
rated load is only guaranteed at 0 °C (32 °F) or
higher.
If temperature exceeds ambient temperature
limits, extra air conditioning of the cabinet or
installation site is required.
9.3.1 Gases
Aggressive gases, such as hydrogen sulphide, chlorine, or
ammonia can damage the electrical and mechanical
components. The unit uses conformal-coated circuit boards
to reduce the eects of aggressive gases. For conformal-
coating class specications and ratings, see
chapter 7.5 Ambient Conditions.
9.3.2 Dust
When installing the drive in dusty environments, pay
attention to the following:
Periodic maintenance
When dust accumulates on electronic components, it acts
as a layer of insulation. This layer reduces the cooling
capacity of the components, and the components become
warmer. The hotter environment decreases the life of the
electronic components.
Keep the heat sink and fans free from dust build-up. For
more service and maintenance information, refer to the
operating guide.
Cooling fans
Fans provide airow to cool the drive. When fans are
exposed to dusty environments, the dust can damage the
fan bearings and cause premature fan failure. Also, dust
can accumulate on fan blades causing an imbalance which
prevents the fans from properly cooling the unit.
9.3.3 Potentially Explosive Atmospheres
WARNING
EXPLOSIVE ATMOSPHERE
Do not install the drive in a potentially explosive
atmosphere. Install the unit in a cabinet outside of this
area. Failure to follow this guideline increases risk of
death or serious injury.
Systems operated in potentially explosive atmospheres
must fulll special conditions. EU Directive 94/9/EC
(ATEX 95) classies the operation of electronic devices in
potentially explosive atmospheres.
Class d species that if a spark occurs, it is
contained in a protected area.
Class e prohibits any occurrence of a spark.
Motors with class d protection
Does not require approval. Special wiring and containment
are required.
Mechanical Installation Con... Design Guide
MG16C302 Danfoss A/S © 11/2017 All rights reserved. 159
9 9

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish

Related product manuals