Parameters
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
+
-
FC
e30bb927.11
A53
U - I
4 - 20mA
Function Setting
Parameter 6-12 T
erminal 53 Low
Current
4 mA*
Parameter 6-13 T
erminal 53 High
Current
20 mA*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0 RPM
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
1500 RPM
*=Default value
Notes/comments:
Table 12.4 Wiring Conguration for Analog Speed Reference
(Current)
12.3 Wiring Congurations for Start/Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB802.10
Function Setting
Parameter 5-10 T
erminal 18
Digital Input
[8] Start*
Parameter 5-12 T
erminal 27
Digital Input
[0] No
operation
Parameter 5-19 T
erminal 37 Safe
Stop
[1] Safe
Torque O
Alarm
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
Table 12.5 Wiring Conguration for Start/Stop Command with
Safe Torque O
130BB805.12
Speed
Start/Stop (18)
Illustration 12.1 Start/Stop with Safe Torque O
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB803.10
Function Setting
Parameter 5-10 T
erminal 18
Digital Input
[9] Latched
Start
Parameter 5-12 T
erminal 27
Digital Input
[6] Stop
Inverse
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
Table 12.6 Wiring Conguration for Pulse Start/Stop
Speed
130BB806.10
Latched Start (18)
Stop Inverse (27)
Illustration 12.2 Latched Start/Stop Inverse
Application Examples Design Guide
MG16C302 Danfoss A/S © 11/2017 All rights reserved. 209