3.6.23 Electrical Installation, Control Cables
Switch Mode
Power Supply
10Vdc
15mA
24Vdc
130/200mA
Analog Output
0/4-20 mA
50 (+10 V OUT)
S201
S202
ON/I=0-20mA
OFF/U=0-10V
+10 Vdc
-10 Vdc
+10 Vdc
0/4-20 mA
-10 Vdc
+10 Vdc
0/4-20 mA
53 (A IN)
54 (A IN )
55 (COM A IN )
(COM A OUT) 39
(A OUT) 42
12 (+24V OUT )
13 (+24V OUT )
18 (D IN)
19 (D IN )
20 (COM D IN)
27 (D IN/OUT )
24 V
24 V
OV
OV
29 (D IN/OUT )
32 (D IN )
33 (D IN )
37 (D IN )
5 6 7 8 5 6 7 8
11
CI45
MODULE
CI45
MODULE
CI45
MODULE
CI45
MODULE
CI45
MODULE
12 13 14 11 12 13 14 11 12 13 14 11 12 13 14 11 12 13 14
15 16 17 1815 16 17 1815 16 17 1815 16 17 1815 16 17 18
5 6 7 8 5 6 7 8 5 6 7 8
1 12 23 34 4 1 2 3 4 1 2 3 4 1 2 3 4
P 5-00
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
ON=Terminated
OFF=Open
(PNP) = Source
(NPN) = Sink
RS-485
(COM RS-485) 61
(P RS-485) 68
(N RS-485) 69
RS - 485
Interface
S801
S801
5V
ON
ON
ON
1
1
1
2
2
2
CONTROL CARD CONNCECTION
130BB759.10
Illustration 3.79
A=Analog, D=Digital
*Terminal 37 (optional) is used for Safe Torque Off. For Safe Torque Off installation instructions, refer to the Safe Torque Off
Operating Instructions for Danfoss VLT
®
Frequency Converters.
**Do not connect cable screen.
How to Install
VLT AQUA Drive FC 202 Operation Instructions
MG20P402 - Rev. 2013-12-16 63
3 3