Programming Guide | VLT® AutomationDrive FC 360
Option Name Description
[0] Disabled Disable the function.
[1] Enabled Enable the function.
[2] When Activated This option requires activation by digital
input or configurable control word.
4-82 Power Limit Motor Mode
Default value: 100.0% Parameter type: Range (0.0–200.0%)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
The power limit motor mode is defined according to the motor power in parameter 1-20 Motor Power.
4-83 Power Limit Generator Mode
Default value: 100.0% Parameter type: Range (0.0–200.0%)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
The power limit generator mode is defined according to the motor power in parameter 1-20 Motor Power.
4.5.8 4-9* Directional Limits
4-90 Directional Limit Mode
Default value: [0] Disabled Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select whether the directional limits are enabled. With directional limits enabled, it is possible to specify different speed and torque limits
for clockwise and counterclockwise rotation directions.
Option Name
[0] Disabled
[1] Speed
[2] Torque
[3] Speed and Torque
4-92 Positive Speed Limit [Hz]
Default value: Size related Parameter type: Range (0.0–500.0 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True