Programming Guide | VLT® AutomationDrive FC 360
2-39 Mech. Brake w/ dir. Change
Default value: [0] OFF Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Enable or disable the mechanical brake function when the shaft changes direction.
Option Name Description
[0] OFF Disable the mechanical brake function
when the shaft changes direction.
[1] ON Enable the mechanical brake function
when the shaft changes direction.
[2] ON with start delay The start delay time is set in parameter
1-71 Start Delay.
4.4 Parameter Group 3-** Reference/Ramps
4.4.1 3-0* Reference Limits
Parameters for setting the reference unit, limits, and ranges.
3-00 Reference Range
Default value: [0] Min - Max Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the range of the reference signal and the feedback signal.
Option Name Description
[0] Min - Max Select the range of the reference signal
and the feedback signal. Signal values can
be positive only, or positive and negative.
[1] -Max - +Max For both positive and negative values
(both directions), relative to parameter
4-10 Motor Speed Direction.
3-01 Reference/Feedback Unit
Default value: Size related Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the unit to be used in Process PID Control references and feedback.