Option Name Description
[0] Disabled No OVC required.
[1] Enabled (not at stop) Activate OVC except when using a stop
signal to stop the drive.
[2] Enabled Activate OVC.
 CAUTION
PERSONAL INJURY AND
EQUIPMENT DAMAGE
Enabling OVC in hoisting
applications may lead to personal
injuries and equipment damage.
l DO NOT enable OVC in
hoisting applications.
2-19 Over-voltage Gain
Default value: 100% Parameter type: Range (0–1000%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
This parameter enables the user to fine-tune the Over-voltage gain for parameter 2-17 Over-voltage Control. It is not necessary to
change this parameter for normal applications.
4.3.3 2-2* Mechanical Brake
2-20 Release Brake Current
Default value: 0.00 A Parameter type: Range (0.00–100.00 A)
Setup: All setups Conversion index: -2
Data type: Uint32 Change during operation: True
Set the motor current for release of the mechanical brake when a start condition is present.
 NOTICE
When mechanical brake control output is selected, but no mechanical brake is connected, the function does not work by default
setting due to too low motor current.
2-22 Activate Brake Speed [Hz]
Default value: 0.0 Hz Parameter type: Range (0.0–400.0 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True