5-42 Off Delay, Relay
Default value: 0.01 s Parameter type: Range (0.00–600.00 s), Array
[2]
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Enter the delay of the relay cutout time.
Off delay
P 5-42
e30ba172.11
Figure 29: Off Delay, Relay
If the selected event condition changes before the on- or off delay timer expires, the relay output is unaffected.
4.6.5 5-5* Pulse Input
The pulse input parameters are used to define an appropriate window for the impulse reference area by configuring the scaling and
filter settings for the pulse inputs. Input terminals 29 or 33 act as frequency reference inputs. Set terminal 29 (parameter 5-13 Terminal
29 Digital Input) or terminal 33 (parameter 5-15 Terminal 33 Digital Input) to [32] Pulse input. If terminal 29 is used as an input, then set
parameter 5-02 Terminal 29 Mode to [0] Input.
Low freq.
P 5-50/
P 5-55
Input
(Hz)
High freq.
P 5-51/
P 5-56
Low
ref.
Figure 30: Pulse Input
5-50 Term. 29 Low Frequency
Default value: 4 Hz Parameter type: Range (4–31999 Hz)
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
136 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360