Setup: 1 setup Conversion index: -2
Data type: Uint16 Change during operation: True
Set the output frequency transferred to the output terminal 29 when the terminal is configured as [48] Bus Ctrl Timeout in parameter
5-63 Terminal 29 Pulse Output Variable and a timeout is detected.
4.7 Parameter Group 6-** Analog In/Out
4.7.1 Introduction
Parameter group for setting up the analog I/O configuration and the digital output.
The drive provides 2 analog inputs:
l Terminal 53
l Terminal 54
The analog inputs can be freely allocated to either voltage (0–10 V) or current input (0/4–20 mA).
4.7.2 6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
Default value: 10 s Parameter type: Range (1–99 s)
Setup: All setups Conversion index: 0
Data type: Uint8 Change during operation: True
Enter the timeout time.
6-01 Live Zero Timeout Function
Default value: [0] Off Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the timeout function. The function set in parameter 6-01 Live Zero Timeout Function is activated if the input signal on terminal
53 or 54 is below 50% of the value in parameter 6-10 Terminal 53 Low Voltage, parameter 6-12 Terminal 53 Low Current, parameter 6-20
Terminal 54 Low Voltage, or parameter 6-22 Terminal 54 Low Current for a time period defined in parameter 6-00 Live Zero Timeout Time.
Option Name
[0] Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
144 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360