l Enter the X
h
value manually. Obtain the value from the motor supplier.
l Use the X
h
default setting. The drive establishes the setting based on the motor nameplate data.
1-36 Iron Loss Resistance (Rfe)
Default value: Size related Parameter type: Range (0.000–2147483.647
Ohm)
Setup: All setups Conversion index: -3
Data type: Uint32 Change during operation: False
Enter the equivalent iron loss resistance value, Rfe. The iron loss resistance value cannot be found by performing an AMA. If Rfe is
unknown, use the default setting for this parameter.
1-37 d-axis Inductance (Ld)
Default value: Size related Parameter type: Range (0.001–65535.000 mH)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: False
Enter the value of the d-axis inductance. Obtain the value from the permanent magnet motor data sheet or perform an AMA on a cold
motor.
1-38 q-axis Inductance (Lq)
Default value: Size related Parameter type: Range (0.001–65535.000 mH)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: False
Set the value of the q-axis inductance. Find the value in the motor data sheet or perform an AMA on a cold motor.
1-39 Motor Poles
Default value: Size related Parameter type: Range (2–100)
Setup: All setups Conversion index: 0
Data type: Uint8 Change during operation: False
Enter the number of motor poles. The motor pole value is always an even number, because it refers to the total pole numbers, not pairs
of poles.
4.2.5 1-4* Adv. Motor Data II
Set parameters for advanced motor data.
1-40 Back EMF at 1000 RPM
Default value: Size related Parameter type: Range (1–9000 V)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: False
62 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360