Programming Guide | VLT® AutomationDrive FC 360
Enter the low frequency limit corresponding to the low motor shaft speed (which is low reference value) in parameter 5-52 Term. 29 Low
Ref./Feedb. Value.
5-51 Term. 29 High Frequency
Default value: 32000 Hz Parameter type: Range (5–32000 Hz)
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
Enter the high frequency limit corresponding to the high motor shaft speed (which is high reference value) in parameter 5-53 Term. 29
High Ref./Feedb. Value.
5-52 Term. 29 Low Ref./Feedb. Value
Default value: 0.000 Parameter type: Range (-4999.000–4999.000)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Enter the low reference value limit for the motor shaft speed [Hz]. This value is also the lowest feedback value. See also parameter
5-57 Term. 33 Low Ref./Feedb. Value. Set terminal 29 to digital input (parameter 5-02 Terminal 29 Mode = [0] Input and parameter 5-13
Terminal 29 Digital Input = applicable value).
5-53 Term. 29 High Ref./Feedb. Value
Default value: Size related Parameter type: Range (-4999.000–4999.000)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Enter the high reference value [Hz] for the motor shaft speed, and the high feedback value. See also parameter 5-58 Term. 33 High Ref./
Feedb. Value. Select terminal 29 as a digital input (parameter 5-02 Terminal 29 Mode = [0] Input (default) and parameter 5-13 Terminal 29
Digital Input = applicable value).
5-54 Term.29 Pulse Filter Time Constant
Default value: 100 ms Parameter type: Range (1–1000 ms)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: False
Enter the pulse filter time constant. The pulse filter dampens oscillations of the feedback signal, an advantage when there is a lot of
noise. A high value results in better dampening but also increases the time delay through the filter.
5-55 Term. 33 Low Frequency
Default value: 4 Hz Parameter type: Range (4–31999 Hz)
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
Enter the low frequency corresponding to the low motor shaft speed (which is low reference value) in parameter 5-57 Term. 33 Low Ref./
Feedb. Value.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 137

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals