Programming Guide | VLT® AutomationDrive FC 360
Enter the low frequency limit corresponding to the low motor shaft speed (which is low reference value) in parameter 5-52 Term. 29 Low
Ref./Feedb. Value.
5-51 Term. 29 High Frequency
Default value: 32000 Hz Parameter type: Range (5–32000 Hz)
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
Enter the high frequency limit corresponding to the high motor shaft speed (which is high reference value) in parameter 5-53 Term. 29
High Ref./Feedb. Value.
5-52 Term. 29 Low Ref./Feedb. Value
Default value: 0.000 Parameter type: Range (-4999.000–4999.000)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Enter the low reference value limit for the motor shaft speed [Hz]. This value is also the lowest feedback value. See also parameter
5-57 Term. 33 Low Ref./Feedb. Value. Set terminal 29 to digital input (parameter 5-02 Terminal 29 Mode = [0] Input and parameter 5-13
Terminal 29 Digital Input = applicable value).
5-53 Term. 29 High Ref./Feedb. Value
Default value: Size related Parameter type: Range (-4999.000–4999.000)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Enter the high reference value [Hz] for the motor shaft speed, and the high feedback value. See also parameter 5-58 Term. 33 High Ref./
Feedb. Value. Select terminal 29 as a digital input (parameter 5-02 Terminal 29 Mode = [0] Input (default) and parameter 5-13 Terminal 29
Digital Input = applicable value).
5-54 Term.29 Pulse Filter Time Constant
Default value: 100 ms Parameter type: Range (1–1000 ms)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: False
Enter the pulse filter time constant. The pulse filter dampens oscillations of the feedback signal, an advantage when there is a lot of
noise. A high value results in better dampening but also increases the time delay through the filter.
5-55 Term. 33 Low Frequency
Default value: 4 Hz Parameter type: Range (4–31999 Hz)
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
Enter the low frequency corresponding to the low motor shaft speed (which is low reference value) in parameter 5-57 Term. 33 Low Ref./
Feedb. Value.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 137