Power [kW (hp)]
Bussmann Type
RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
22 (30)
KTS-R-50
JKS-50
JJS-50
30 (40)
KTS-R-60
JKS-60
JJS-60
37 (50)
KTS-R-80
JKS-80
JJS-80
45 (60)
KTS-R-100
JKS-100
JJS-100
55 (75)
KTS-R-125
JKS-125
JJS-125
75 (100)
KTS-R-150
JKS-150
JJS-150
90 (125)
KTS-R-175
JKS-175
JJS-175
Table 68: Recommended Maximum Fuse, 525–690 V, Enclosure Sizes B, and C
Power
[kW (hp)]
Maxi-
mum
prefuse
[A]
Bussmann
E52273
RK1/JDDZ
Buss-
mann
E4273 J/
JDDZ
Buss-
mann
E4273 T/
JDDZ
SIBA E180276
RK1/JDDZ
Littelfuse
E81895
RK1/JDDZ
Ferraz Shaw-
mut E163267/
E2137 RK1/
JDDZ
Ferraz
Shawmut
E2137
J/HSJ
11–15
(15–20)
30
KTS-R-30
JKS-30
JKJS-30
5017906-030
KLS-R-030
A6K-30-R
HST-30
18.5 (25.0)
45
KTS-R-45
JKS-45
JJS-45
5014006-050
KLS-R-045
A6K-45-R
HST-45
30 (40)
60
KTS-R-60
JKS-60
JJS-60
5014006-063
KLS-R-060
A6K-60-R
HST-60
37 (50)
80
KTS-R-80
JKS-80
JJS-80
5014006-080
KLS-R-075
A6K-80-R
HST-80
45 (60)
90
KTS-R-90
JKS-90
JJS-90
5014006-100
KLS-R-090
A6K-90-R
HST-90
55 (75)
100
KTS-R-100
JKS-100
JJS-100
5014006-100
KLS-R-100
A6K-100-R
HST-100
75 (100)
125
KTS-R-125
JKS-125
JJS-125
2028220-125
KLS-150
A6K-125-R
HST-125
90 (125)
150
KTS-R-150
JKS-150
JJS-150
2028220-150
KLS-175
A6K-150-R
HST-150
8.11 Connection Tightening Torques
Table 69: Tightening Torque for Cables
En-
clo-
sure
size
200–
240 V [kW
(hp)]
380–
480/500 V
[kW (hp)]
525–600 V
[kW(hp)]
525–
690 V
[kW
(hp)]
Mains [Nm
(in-lb)]
Motor [Nm
(in-lb)]
DC
con-
nec-
tion
[Nm
(in-lb)]
Brake
[Nm
(in-lb)]
Ground
[Nm (in-
lb)]
Re-
lay
[Nm
(in-
lb)]
A2
1.1–2.2
(1.5–3.0)
1.1–4.0 (1.5–
5.0)
0.6
0.6
0.6
1.8
3.0
0.6
A3
3.0–3.7
(4.0– 5.0)
5.5–7.5 (7.5–
10)
1.1–7.5
(1.5–10)
1.1–7.5
(1.5–
10.0)
0.6
0.6
0.6
1.8
3.0
0.6
A4
1.1–2.2
(1.5–3.0)
1.1–4.0 (0.5–
5.0)
0.6
0.6
0.6
1.8
3.0
0.6
A5
1.1–3.7
(1.5– 5.0)
1.1–7.5 (1.5–
10)
1.1–7.5
(1.5–10.0)
0.6
0.6
0.6
1.8
3.0
0.6
AQ267037536117en-000101 / 130R0083110 | Danfoss A/S © 2023.09
Specifications
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals