En-
clo-
sure
size
200–
240 V [kW
(hp)]
380–
480/500 V
[kW (hp)]
525–600 V
[kW(hp)]
525–
690 V
[kW
(hp)]
Mains [Nm
(in-lb)]
Motor [Nm
(in-lb)]
DC
con-
nec-
tion
[Nm
(in-lb)]
Brake
[Nm
(in-lb)]
Ground
[Nm (in-
lb)]
Re-
lay
[Nm
(in-
lb)]
B1
5.5–11
(7.5–15)
11–18 (15-24)
11–18
(15-24)
1.8
1.8 (15.9)
1.5
1.5
3.0
0.6
B2
15 (20)
22–30 (30–
40)
22–30 (30–
40)
11–30
(15– 40)
4.5 (39.8)
4.5 (39.8)
3.7
3.7
3.0
0.6
B3
5.5–11
(7.5–15)
11–18 (15-24)
11–18
(15-24)
1.8 (15.9)
1.8 (15.9)
1.8
(15.9)
1.8
(15.9)
3.0
0.6
B4
15–18
(20-24)
22–37 (30–
50)
22–37 (30–
50)
11–37
(15-50)
4.5 (39.8)
4.5 (39.8)
4.5
(39.8)
4.5
(39.8)
3.0
0.6
C1
18–30
(24– 40)
37–55 (50–
75)
37–55 (50–
75)
10 (89)
10 (89)
10 (89)
10 (89)
3.0
0.6
C2
37–45
(50– 60)
75–90 (100–
125)
75–90
(100– 125)
37–90
(50–
125)
14/24
(124/212)
(1)
14/24
(124/212)
(1)
14
(124)
14
(124)
3.0
0.6
C3
22–30
(30–40)
45–55 (60–
75)
45–55 (60–
75)
45–55
(60–75)
10 (89)
10 (89)
10 (89)
10 (89)
3.0
0.6
C4
37–45
(50– 60)
75–90 (100–
125)
75–90
(100– 125)
14/24
(124/212)
(1)
14/24
(124/212)
(1)
14
14
3.0
0.6
1
For different cable dimensions x/y, where x ≤95 mm
2
(3 AWG) and y ≥95 mm
2
(3 AWG).
8.12 Power Ratings, Weight, and Dimensions
Table 70: Power Ratings, Weight, and Dimensions, Enclosure Size A
Enclosure size
A2
A3
A4
A5
Rated pow-
er [kW (hp)]
200–240 V
1.1–2.2 (1.5–3.0)
3.0–3.7 (4.0–5.0)
1.1–2.2 (1.5–
3.0)
1.1–3.7 (1.5–
5.0)
380-480/500 V
1.1–4.0 (1.5–5.0)
5.5–7.5 (7.5–10)
1.1–4.0 (1.5–
5.0)
1.1–7.5 (1.5–
10)
525–600 V
1.1–7.5 (1.5–10)
1.1–7.5 (1.5–
10)
525–690 V
1.1–7.5
(1.5–10)
Protection
rating
IP20(UL
Open
Type)
IP21(UL
Type 1)
IP20(UL
Open
Type)
IP21(UL
Type 1)
IP55/66(UL
Type 12/4X)
IP55/66(UL
Type 12/4X)
Height [mm (in)]
Height of mounting plate
A
(1)
268 (10.6)
375 (14.8)
268 (10.6)
375 (14.8)
390 (15.4)
420 (16.5)
Height with ground ter-
mination plate for field-
bus cables
A
374 (14.7)
374 (14.7)
AQ267037536117en-000101 / 130R0083 | 111Danfoss A/S © 2023.09
Specifications
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals