8.10 Fuses and Circuit Breakers
8.10.1 Fuse Recommendations
Fuses ensure that possible damage to the drive is limited to damage inside the unit. Danfoss recommends fuses and/or circuit
breakers on the supply side as protection. For further information, see Application Note Fuses and Circuit Breakers.
N O T I C E
Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
Recommendations
gG type fuses.
Moeller type circuit breakers. For other circuit breaker types, ensure that the energy into the drive is equal to or lower than the
energy provided by Moeller types.
For further information, see Application Note Fuses and Circuit Breakers.
The recommended fuses in
8.10.2 CE Compliance, 8.10.3 UL Compliance (61800-5-1), and 8.10.4 UL Compliance (508C) are suitable
for use on a circuit capable of 100000 A
rms
(symmetrical), depending on the drive power and voltage rating. See the Electrical Data
section for the short-circuit current rating (SCCR) based on the specific power and voltage rating of the drive.
8.10.2 CE Compliance
Table 56: 200–240 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit break-
er Moeller
Maximum trip
level [A]
A2
1.1–1.5 (1.5–2.0)
gG-10
gG-25
PKZM0-25
25
2.2 (3.0)
gG-16
A3
3.0 (4.0)
gG-16
gG-32
PKZM0-25
25
3.7 (5.0)
gG-20
A4
1.1–1.5 (1.5–2.0)
gG-10
gG-32
PKZM0-25
25
2.2 (3.0)
gG-16
A5
1.1–1.5 (1.5–2.0)
gG-10
gG-32
PKZM0-25
25
2.2–3.0 (3.0–4.0)
gG-16
3.7 (5.0)
gG-20
B1
5.5 (7.5)
gG-25
gG-80
PKZM4-63
63
7.5–11 (10–15)
gG-32
B2
15 (20)
gG-50
gG-100
NZMB1-A100
100
B3
5.5–7.5 (7.5–10)
gG-25
gG-63
PKZM4-50
50
11 (15)
gG-32
B4
15 (20)
gG-50
gG-125
NZMB1-A100
100
18 (24)
gG-63
C1
18 (24)
gG-63
gG-160
NZMB2-A200
160
22 (30)
gG-80
30 (40)
gG-100
aR-160
AQ267037536117en-000101 / 130R0083102 | Danfoss A/S © 2023.09
Specifications
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals