EasyManuals Logo
Home>Danfoss>DC Drives>vlt FC 102

Danfoss vlt FC 102 Operating Guide

Danfoss vlt FC 102
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #103 background imageLoading...
Page #103 background image
Enclosure
Power [kW (hp)]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit break-
er Moeller
Maximum trip
level [A]
C2
37 (50)
aR-160
aR-200
NZMB2-A250
250
45 (60)
aR-200
aR-250
C3
22 (30)
gG-80
gG-150
NZMB2-A200
150
30 (40)
aR-125
aR-160
C4
37 (50)
aR-160
aR-200
NZMB2-A250
250
45 (60)
aR-200
aR-250
Table 57: 380–480 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit break-
er Moeller
Maximum trip
level [A]
A2
1.1–3.0 (1.5–4.0)
gG-10
gG-25
PKZM0-25
25
4.0 (5.0)
gG-16
A3
5.5–7.5 (7.5–10.0)
gG-16
gG-32
PKZM0-25
25
A4
1.1–3.0 (1.5–4.0)
gG-10
gG-32
PKZM0-25
25
4.0 (5.0)
gG-16
A5
1.1–3.0 (1.5–4.0)
gG-10
gG-32
PKZM0-25
25
4.0–7.5 (5.0–10.0)
gG-16
B1
11–18 (15–24)
gG-40
gG-80
PKZM4-63
63
B2
22 (30)
gG-50
gG-100
NZMB1-A100
100
30 (40)
gG-63
B3
11–18 (15–24)
gG-40
gG-63
PKZM4-50
50
B4
22 (30)
gG-50
gG-125
NZMB1-A100
100
30 (40)
gG-63
37 (50)
gG-80
C1
37 (50)
gG-80
gG-160
NZMB2-A200
160
45 (60)
gG-100
55 (75)
gG-160
C2
75 (100)
aR-200
aR-250
NZMB2-A250
250
90 (125)
aR-250
C3
45 (60)
gG-100
gG-150
NZMB2-A200
150
55 (75)
gG-160
gG-160
C4
75 (100)
aR-200
aR-250
NZMB2-A250
250
90 (125)
aR-250
AQ267037536117en-000101 / 130R0083 | 103Danfoss A/S © 2023.09
Specifications
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals