Table 58: 525–600 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit break-
er Moeller
Maximum trip
level [A]
A3
5.5 (7.5)
gG-10
gG-32
PKZM0-25
25
7.5 (10)
gG-16
A5
1.1 (1.5)
gG-10
gG-32
PKZM0-25
25
7.5 (10)
gG-16
B1
11 (15)
gG-25
gG-80
PKZM4-63
63
15 (20)
gG-32
18.5 (25)
gG-40
B2
22 (30)
gG-50
gG-100
NZMB1-A100
100
30 (40)
gG-63
B3
11 (15)
gG-25
gG-63
PKZM4-50
50
15–18.5 (20–25)
gG-32
B4
22 (30)
gG-40
gG-125
NZMB1-A100
100
30 (40)
gG-50
37 (50)
gG-63
C1
37 (50)
gG-63
gG-160
NZMB2-A200
160
45 (60)
gG-100
55 (60)
aR-160
aR-250
C2
75–90 (100–125)
aR-200
aR-250
NZMB2-A250
250
C3
45 (60)
gG-63
gG-150
NZMB2-A200
150
55 (75)
gG-100
C4
75 (100)
aR-160
aR-250
NZMB2-A250
250
90 (125)
aR-200
Table 59: 525–690 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
Recommended fuse
size
Recommended maxi-
mum fuse
Recommended circuit
breaker Moeller
Maximum trip lev-
el [A]
A3
1.1 (1.5)
gG-6
gG-25
PKZM0-16
16
1.5 (2.0)
gG-6
gG-25
2.2 (3.0)
gG-6
gG-25
3.0 (4.0)
gG-10
gG-25
4.0 (5.0)
gG-10
gG-25
5.5 (7.5)
gG-16
gG-25
7.5 (10)
gG-16
gG-25
AQ267037536117en-000101 / 130R0083104 | Danfoss A/S © 2023.09
Specifications
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals