Enclosure
Power [kW (hp)]
Recommended fuse
size
Recommended maxi-
mum fuse
Recommended circuit
breaker Moeller
Maximum trip lev-
el [A]
B2/B4
11 (15)
gG-25
gG-63
15 (20)
gG-32
18 (24)
gG-32
22 (30)
gG-40
B4/C2
30 (40)
gG-63
gG-80
C2/C3
37 (50)
gG-63
gG-100
45 (60)
gG-80
gG-125
C2
55 (75)
gG-100
gG-160
75 (100)
gG-125
8.10.3 UL Compliance (61800-5-1)
Table 60: Recommended Fuse, 200–240 V and 115Y/200–139Y/240, Enclosure Sizes A2, A3, A5, B1, B2, and C1
Power [kW (hp)]
Class
Recommended
Verified with
1.1 (1.5)
J/T/CC
10 A
A2: class J, 20 A
A5: class J, 30 A
1.5 (2.0)
J/T/CC
15 A
A2: class J, 20 A
A5: class J, 30 A
2.2 (3.0)
J/T/CC
20 A
A2: class J, 20 A
A5: class J, 30 A
3.0 (4.0)
J/T/CC
25 A
A3: class J, 30 A
A5: class J, 30 A
3.7 (5.0)
J/T/CC
30 A
A3: class J, 30 A
A5: class J, 30 A
5.5–7.5 (7.5–10)
J/T/CC
50 A
B1: class J, 60 A
11 (15)
J/T/CC
60 A
B1: class J, 60 A
15 (20)
J/T
80 A
B2: class J, 80 A
18.5–22 (25–30)
J/T
125 A
C1: class J, 150 A
30 (40)
J/T
150 A
C1: class J, 150 A
Table 61: Recommended Fuse, 380–480 V and 220Y/380–277Y/480, Enclosure Sizes A2, A3, A5, B1, B2, and C1
Power [kW (hp)]
Class
Recommended
Verified with
1.1 (1.5)
J/T/CC
6 A
A2: class J, 10 A
A5: class J, 30 A
1.5–2.2 (2.0–3.0)
J/T/CC
10 A
A2: class J, 20 A
AQ267037536117en-000101 / 130R0083 | 105Danfoss A/S © 2023.09
Specifications
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals