[20] Freeze output is selected as a function for a digital input (parameter group 5-1* Digital Inputs). The corre-
sponding terminal is active. Speed control is only possible via the terminal options [21] Speed up and [22]
Speed down.
Hold ramp is activated via serial communication.
Freeze out-
put request
A freeze output command was given, but the motor remains stopped until a run permissive signal is received.
Freeze ref.
[19] Freeze reference is selected as a function for a digital input (parameter group 5-1* Digital Inputs). The corre-
sponding terminal is active. The drive saves the actual reference. Changing the reference is now only possible via
terminal options [21] Speed up and [22] Speed down.
Jog request
A jog command was given, but the motor remains stopped until a run permissive signal is received via a digital
input.
Jogging
The motor is running as programmed in parameter 3-19 Jog Speed [RPM].
[14] Jog was selected as a function for a digital input (parameter group 5-1* Digital Inputs). The corresponding
terminal (for example, terminal 29) is active.
The jog function is activated via the serial communication.
The jog function is selected as a reaction for a monitoring function (for example, for the no signal function).
The monitoring function is active.
Motor check
In parameter 1-80 Function at Stop, [2] Motor Check is selected. A stop command is active. To ensure that a motor is
connected to the drive, a permanent test current is applied to the motor.
OVC control
Overvoltage control is activated via parameter 2-17 Over-voltage Control, [2] Enabled. The connected motor sup-
plies the drive with generative energy. The overvoltage control adjusts the V/Hz ratio to run the motor in control-
led mode and to prevent the drive from tripping.
PowerUnit
Off
(Only drives with a 24 V external supply installed). Mains supply to the drive was removed, and the control card is
supplied by the external 24 V.
Protection
md
Protection mode is active. The unit detected a critical status (overcurrent or overvoltage).
To avoid tripping, switching frequency is reduced to 4 kHz.
If possible, protection mode ends after approximately 10 s.
Protection mode can be restricted in parameter 14-26 Trip Delay at Inverter Fault.
QStop
The motor is decelerating using parameter 3-81 Quick Stop Ramp Time.
[4] Quick stop inverse is selected as a function for a digital input (parameter group 5-1* Digital Inputs). The corre-
sponding terminal is not active.
The quick stop function is activated via serial communication.
Ramping
The motor is accelerating/decelerating using the active ramp up/down. The reference, a limit value, or a standstill
is not yet reached.
Ref. high
The sum of all active references is above the reference limit set in parameter 4-55 Warning Reference High.
Ref. low
The sum of all active references is below the reference limit set in parameter 4-54 Warning Reference Low.
Run on ref.
The drive is running in the reference range. The feedback value matches the setpoint value.
Run request
A start command was given, but the motor remains stopped until a run permissive signal is received via digital
input.
Running
The drive drives the motor.
Sleep Mode
The energy-saving function is enabled. The motor has stopped, but restarts automatically when required.
AQ267037536117en-000101 / 130R0083 | 65Danfoss A/S © 2023.09
Diagnostics and Troubleshooting
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals