Symptom
Possible cause
Test
Solution
Motor coast signal active
(Coasting)
Check parameter 5-12 Coast Inv. for
correct setting for terminal 27 (use
default setting).
Apply 24 V on terminal 27 or pro-
gram this terminal to [0] No opera-
tion.
Wrong reference signal
source.
Check the reference signal: Local,
remote, or bus reference? Preset
reference active? Terminal connec-
tion correct? Scaling of terminals
correct? Reference signal available?
Program correct settings. Check pa-
rameter 3-13 Reference Site. Set pre-
set reference active in parameter
group 3-1* References. Check for cor-
rect wiring. Check scaling of termi-
nals. Check reference signal.
AIC not running
Check the following for current:
Parameter 2-70 AIC L1 Current
Parameter 2-71 AIC L2 Current
Parameter 2-72 AIC L3 Current
Troubleshoot the AIC (Active In-
Converter).
Motor running in
wrong direction.
Motor rotation limit.
Check that parameter 4-10 Motor
Speed Direction is programmed cor-
rectly.
Program correct settings.
Active reversing signal.
Check if a reversing command is
programmed for the terminal in pa-
rameter group 5-1* Digital inputs.
Deactivate reversing signal.
Wrong motor phase connec-
tion.
See 5.3.7 Checking Motor Rotation
Motor does not
reach maximum
speed.
Frequency limits are set
wrong.
Check output limits in parameter
4-13 Motor Speed High Limit [RPM],
parameter 4-14 Motor Speed High
Limit [Hz], and parameter 4-19 Max
Output Frequency.
Program correct limits.
Reference input signal not
scaled correctly.
Check the reference input signal
scaling in parameter group 6-0* An-
alog I/O Mode and parameter group
3-1* References. Reference limits in
parameter group 3-0* Reference Lim-
its.
Program correct settings.
Motor speed un-
stable.
Possible incorrect parameter
settings.
Check the settings of all motor pa-
rameters, including all motor com-
pensation settings. For closed-loop
operation, check PID settings.
Check settings in parameter group
1-6* Load Depend. Setting. For
closed-loop operation, check set-
tings in parameter group 20-0* Feed-
back.
Motor runs rough.
Possible overmagnetization.
Check for incorrect motor settings
in all motor parameters.
Check motor settings in parameter
groups 1-2* Motor Data, 1-3* Adv Mo-
tor Data, and 1-5* Load Indep. Set-
ting.
Motor does not
brake.
Possible incorrect settings in
the brake parameters. Possi-
ble too short ramp-down
times.
Check the brake parameters.
Check parameter groups 2-0* DC
Brake and 3-0* Reference Limits.
Open power fuses
or circuit breaker
trip
Phase-to-phase short.
Motor or panel has a short phase.
Check motor and panel phase for
shorts.
Eliminate any short circuits detec-
ted.
AQ267037536117en-000101 / 130R0083 | 83Danfoss A/S © 2023.09
Diagnostics and Troubleshooting
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals