ASDA-A2 Chapter 6 Control Mode of Operation
Revision February, 2017 6-39
P2-43 NCF2 Resonance Suppression (Notch filter) (2)
Address: 0256H
0257H
Operational
Interface:
Panel / Software Communication
Related Section:
6.3.7
Default:
1000
Control
Mode:
ALL
Unit:
Hz
Range:
50 ~ 2000
Data Size:
16-bit
Format:
Decimal
Settings:
The second setting value of resonance frequency. If P2-44 is set to 0,
this function is disabled. P2-23 and P2-24 are the first Notch filter.
P2-44 DPH2
Resonance Suppression (Notch filter)
Attenuation Rate (2)
Address: 0258H
0259H
Operational
Interface:
Panel / Software Communication
Related Section:
6.3.7
Default:
0
Control
Mode:
ALL
Unit:
dB
Range:
0 ~ 32 (0: disable Notch filter)
Data Size:
16-bit
Format:
Decimal
Settings:
The second resonance suppression (notch filter) attenuation rate.
When this parameter is set to 0, the function of Notch filter is disabled.
NOTE
If the value of attenuation rate is set to 5, then it would be -5dB.
P2-46 DPH3
Resonance Suppression (Notch filter)
Attenuation Rate (3)
Address: 025CH
025DH
Operational
Interface:
Panel / Software Communication
Related Section:
6.3.7
Default:
0
Control
Mode:
ALL

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ECMA-E 1315 Series and is the answer not in the manual?

Delta ECMA-E 1315 Series Specifications

General IconGeneral
BrandDelta
ModelECMA-E 1315 Series
CategoryServo Drives
LanguageEnglish

Related product manuals