49
Ultron NT Series
'XULQJLQVWDOODWLRQHQVXUHWKDWWKH836LQSXWQHXWUDOLV¿UPO\FRQQHFWHGWRWKH
utility power neutral.
19. The top cover of UPS model 260kVA~500kVA is designed with air flow
YHQWLODWLRQKROHV(QVXUHWKDWWKHUHLVQRGXVWRUOLTXLGGURSSLQJIURPWKHWRSRI
the UPS.
4.7 Floor Weight Loading Table
UPS
Input voltage: 400/ 230V (3ĭ4W)
Output voltage: 400/ 230V (3ĭ4W)
UPS rating
(kVA)
10 15 20 30 40 50 60 80 100 120 160 200 260 320 400 500
Weight
(Kg)
335 335 365 365 425 460 506 525 700 745 1050 1085 1680 1720 1920 2410
Weight
loading
(kg/m
2
)
698 698 760 760 885 958 1054 1094 1054 1122 1054 1089 1055 1080 1206 1346
,QSXWYROWDJHǻ9ĭ3W)
Output voltage : 208/ 120V (3ĭ4W)
UPS rating (kVA)
100
Weight (Kg)
1125
Weight loading (kg/m
2
)
1130
External Battery Cabinet
Battery Type
(AH)
12V/ 26AH
x 29PCS
12V/ 40AH
x 29PCS
12V/ 26AH
x 58PCS
12V/ 40AH
x 58PCS
12V/ 100AH
x 29PCS
Weight
(Kg)
360 520 796 1118 1420
Weight
loading
(kg/m
2
)
750 1084 1066 1497 1764