Chapter 7 UPS Operation
88
,IWKHEDWWHU\WHVWLVQRUPDOXVHDYROWDJHPHWHUWRPHDVXUHWKH836¶VRXWSXW
voltage (per phase). If normal, turn on the UPS Output breaker or switch.
7.2.2 Battery Mode Start-up Procedures (Single)
NOTE :
1. Before executing the following start-up procedures, please refer to 7.1
3UH6WDUWXS3UH7XUQR௺:DUQLQJV¿UVW
2. Battery start function is customized and only applicable to the model that
has the built-in battery contactor.
7XUQRQHDFKH[WHUQDOEDWWHU\FDELQHW¶VBattery breaker.
2. Press the battery start-up switch once.
$IWHUWKH'&%86YROWDJHUHDFKHVDURXQG9WKH836¶VEDWWHU\FRQWDFWRUZLOO
start up.
4. Press the ‘ON¶DQGµ
¶EXWWRQVVLPXOWDQHRXVO\IRUVHFRQGV$IWHUWKDWWKH
inverter will start up, the inverter voltage will be established and the LCD will
display ‘Backup Mode¶
5. Measure the voltage of the UPS Output breaker or switch. If normal, turn on the
UPS Output breaker or switch.
7.2.3 Manual Bypass Mode Start-up Procedures (Single)
NOTE :
5HJXODU836PDLQWHQDQFHDWDIUHTXHQF\RIHYHU\KDOI\HDULVVXJJHVWHG
2. Before executing the following procedures, please refer to 7.1 Pre Start-
XS3UH7XUQR௺:DUQLQJV¿UVW
The Manual Bypass breaker or switch can only be turned ON for UPS
PDLQWHQDQFHZKLFKHQVXUHVWKDWWKHSRZHUVXSSO\LQJWRWKHFRQQHFWHGORDGVZRQ¶W
be interrupted during maintenance process.
If the Manual Bypass breaker or switch is turned ON in Normal Mode, the inverter
will be turned OFF, the connected critical loads will be power-supplied by the
PDQXDOE\SDVVDQGWKHRXWSXWZRQ¶WEHSURWHFWHG3OHDVHHQVXUHWKDWWKHUHVHUYH
AC power is normal.