87
Ultron NT Series
Chapter 7 : UPS Operation
3UH6WDUWXS3UH7XUQRႇ:DUQLQJV
z
Please check the following items before start-up of the UPS.
1. All circuit breakers or switches are in the OFF position.
(DFKH[WHUQDOEDWWHU\FDELQHW¶VEDWWHU\EUHDNHULVLQWKHOFF status.
3. Ensure that neutral line and grounding have the same voltage.
%HIRUHVXSSO\LQJSRZHUWRWKH836FKHFNWKDWLQSXWYROWDJHIUHTXHQF\DQG
SKDVHVHTXHQFHDUHPHWZLWK836VSHFL¿FDWLRQV
5. Ensure that every fuse is in the ‘CONNECTION¶VWDWXV
z
3OHDVHUHDGWKHIROORZLQJEHIRUHWXUQLQJRႇWKH836
If you perform turn-off procedures, all power supplying to the UPS will be
completely cut off. Please make sure the critical loads connected to the UPS
KDYHDOUHDG\EHHQVDIHO\VKXWGRZQEHIRUH\RXSHUIRUPWKHWXUQRႇSURFHGXUHV
7.2 Start-up Procedures
7.2.1 Normal Mode Start-up Procedures (Single)
NOTE :
Before executing the following start-up procedures, please refer to 7.1
3UH6WDUWXS3UH7XUQR௺:DUQLQJV¿UVW
1. Turn on the Reserve Input breaker or switch, and the LCD will display ‘Bypass
Mode¶
2. Turn on the 5HFWL¿HU,QSXW breaker or switch and wait about 30 seconds. After
that, the DC BUS voltage will be established to 393V.
7XUQRQHDFKH[WHUQDOEDWWHU\FDELQHW¶VBattery breaker.
4. Press the ‘ON¶DQGµ
¶EXWWRQVVLPXOWDQHRXVO\IRUVHFRQGV$IWHUWKDWWKH
inverter will start up. Once the inverter voltage is established, the power will be
switched from bypass to inverter. At this moment, it will be the inverter to supply
power to the connected loads, and the LCD will display ‘Normal Mode¶$IWHU
30 seconds, the UPS will automatically execute a battery test to check if the
connected batteries are normal or not.