IQ DP-4000
SECTION 2 - HARDWARE DESCRIPTION TD 17548B
7
2.2.3 Metering Specifications
Table 2.C shows the metering specifications for the IQ
DP-4000.
Item
Displayed
through
PowerNet
Local Display
AC Amperes Phases
A, B, C
+/- 0.3% +/- 0.3% +/- 1 digit
AC Voltage
Phase A-B, B-C, C-A
Phase A-N,
B-N, C-N
+/- 0.3%
+/- 0.3%
+/- 0.3% +/- 1 digit
+/- 0.3% +/- 1 digit
Watts +/- 0.6% +/- 0.6% +/- 1 digit
Vars +/- 0.6% +/- 0.6% +/- 1 digit
VA +/- 0.6% +/- 0.6% +/- 1 digit
Watt-hours +/- 0.6% +/- 0.6% +/- 1 digit
Var-hours +/- 0.6% +/- 0.6% +/- 1 digit
VA-hours +/- 0.6% +/- 0.6% +/- 1 digit
Power Factor +/- 1 % +/- 1 %
Frequency +/- 0.1Hz +/- 0.1 Hz
% THD Through 31st Harmonic
Table 2.C Metering Specifications
Accuracy is maintained from 3% to 250% of the full
scale of the device.
Nominal Full Scale Current: 5 Amps ac
Nominal Full Scale Voltage: 120-600 Vac
Certification
UL / cUL: Listed UL-508, File E62791, NKCR Auxiliary Devices (with IQM3PPM)
Listed UL-3111, File E185559, Metering (with IQMSSPM, IQMDCPM)
NEMA: 3R, 12 (with supplied gasket)
FCC: Part 15, Class A
CISPR: CISPR-11 Class A
CE: Units marked with CE comply with IEC 1010-1 (1990) incl. Amend 1&2 (1995)
EN61010-1 (1993), CSA C22.2#1010.1 (1992), and EN50082-2 (1994)