IQ DP-4000
SECTION 5 - PROGRAMMING THE IQ DP-4000 TD 17548B
36
= OFF = ON
Ranges Switch Settings
(Set all 8 S2 switches)
Load Shed,
% of nominal
Rotary
Switch
S3.E S3.D
Setpoint
Switch
S2.1 S2.2 S2.3 S2.4 S2.5 S2.6
Restore Load,
% of nominal
Rotary
Switch
S3.E S3.D
Setpoint
Switch
S2.5 S2.6 S2.7 S2.8 S2.7 S2.8
10 off off off off off off
12 on off off off off off
14 off on off off off off
16 on on off off off off
18 off off on off off off
20 on off on off off off
22 off on on off off off
24 on on on off off off
26 off off off on off off
28 on off off on off off
30 off on off on off off
32 on on off on off off
34 off off on on off off
36 on off on on off off
38 off on on on off off
40 on on on on off off
42 off off off off on off
44 on off off off on off
46 off on off off on off
48 on on off off on off
50 off off on off on off
52 on off on off on off
54 off on on off on off
56 on on on off on off
58 off off off on on off
60 on off off on on off
62 off on off on on off
64 on on off on on off
66 off off on on on off
68 on off on on on off
70 off on on on on off
72 on on on on on off
74 off off off off off on
76 on off off off off on
78 off on off off off on
80 on on off off off on
82 off off on off off on
Table 5.Y Load Shed and Restore Load Settings (continued on next page)