In order to ensure the installation meets the various emission standards
described in:
• The EMC data sheet available from the supplier of the drive
• The Declaration of Conformity at the front of this manual
• Chapter 12 Technical data on page 228
...the correct external EMC filter must be used and all of the guidelines in
section 4.11.3 General requirements for EMC and section
4.11.5 Compliance with generic emission standards must be followed.
Table 4-13 Affinity EMC filter cross reference
Table 4-14 IP54 EMC filter cross reference
N
The installer of the drive is responsible for ensuring compliance with the
EMC regulations that apply where the drive is to be used.
4.11.1 Grounding hardware
The drive is supplied with a grounding bracket, and sizes 1 to 3 with a
grounding clamp, to facilitate EMC compliance. They provide a
convenient method for direct grounding of cable shields without the use
of "pig-tails". Cable shields can be bared and clamped to the grounding
bracket using metal clips or clamps
1
(not supplied) or cable ties. Note
that the shield must in all cases be continued through the clamp to the
intended terminal on the drive, in accordance with the connection details
for the specific signal.
1
A suitable clamp is the Phoenix DIN rail mounted SK14 cable clamp
(for cables with a maximum outer diameter of 14mm).
See Figure 4-15 and Figure 4-16 for details on installing the grounding
clamp.
See Figure 4-17 for details on installing the grounding bracket.
Figure 4-15 Installation of grounding clamp (size 1 and 2)
Figure 4-16 Installation of grounding clamp (size 3)
Figure 4-17 Installation of grounding bracket (sizes 1 to 6)
Drive
Schaffner Epcos
CT part no. CT part no.
BA1201 to BA1202 4200-6118 4200-6121
BA1203 to BA1204 4200-6119 4200-6120
BA2201 to BA2203 4200-6210 4200-6211
BA3201 to BA3202 4200-6307 4200-6306
BA4201 to BA4203 4200-6406 4200-6405
BA5201 to BA5202 4200-6503 4200-6501
BA1401 to BA1404 4200-6118 4200-6121
BA1405 to BA1406 4200-6119 4200-6120
BA2401 to BA2403 4200-6210 4200-6211
BA3401 to BA3403 4200-6305 4200-6306
BA4401 to BA4403 4200-6406 4200-6405
BA5401 to BA5402 4200-6503 4200-6501
BA6401 to BA6402 4200-6603 4200-6601
BA3501 to BA3507 4200-6309 4200-6308
BA4601 to BA4606 4200-6408 4200-6407
BA5601 to BA5602 4200-6504 4200-6502
BA6601 to BA6602 4200-6604 4200-6602
Drive CT part no.
BA1201 to BA1202 4200-6125
BA1203 to BA1204 4200-6124
BA1401 to BA1404 4200-6125
BA1405 to BA1406 4200-6124
BA2201 to BA2203 4200-6218
BA2401 to BA2403 4200-6218
BA3201 to BA3202 4200-6319
BA3401 to BA3403 4200-6318
BA3501 to BA3502 4200-6320
High ground leakage current
When an EMC filter is used, a permanent fixed ground
connection must be provided which does not pass through a
connector or flexible power cord. This includes the internal
EMC filter.