1592001530 XC15-35CX EN r1.2 11.04.2017 XC15-35CX 22/40
dLt
Temperature value for compressor warning:
- P3, P4=NTC -40 to 110°C; -40 to 230°F
- P3, P4=NTC86k -40 to 180°C; -40 to 356°F
- P3, P4=PT1000 -40 to 180°C; -40 to 356°F
dth
Differential for DLT alarm deactivation: 0.1 to 25.5°C; 1 to 50°F
dLd
Delay in DLT alarm activation: 0 to 255 sec
dCt
Cooling time after detecting a DLT alarm: 0 to 255 min
dLn
Number of DLT alarms detected before activating the compressor lockout: (0
to 15) after detecting dLn alarms DLT type during dLi hours the regulation will be
stopped. With dLn=0 this function is disabled.
dLi
Interval of time for DLT alarm management: (0 to 24 hours) with dLi=0 this
function is disabled.
CEd
Maximum compressor capacity (in percentage): (10 to PMA) the maximum
capacity will be limited to this value in case of:
- Temperature probe error when dLP=P3, P4;
- Regulation probe error (for compressor)
Cdd
Maximum compressor capacity (in percentage) in case of DLT alarm: (10 to
PMA) the maximum compressor capacity will be limited to this value, for dLd time,
in case of a DLT warning (valid both for Digital or inverter-controlled compressors).
15.7 COMPRESSOR SAFETIES
odS
Output delay activation at start-up: (0 to 255 sec) after start-up, the compressor
output will be activated after the delay odS.
Con
Compressor ON time in case of regulation probe error: (0 to 255 min) used only
for ON-OFF compressors
CoF
Compressor OFF time in case of regulation probe error: (0 to 255 min) used
only for ON-OFF compressors
2on
Delay between two consecutive activation of the same compressor: 0 a 255
min
2oF
Delay between deactivation and next activation of the same compressor: 0 to
255 min
don
Delay before activating another compressor: 0.0 to 99min00sec, res. 10 sec
doF
Delay before deactivating another compressor: 0.0 to 99min00sec, res. 10 sec
dnF
Minimum compressor ON time: 0.0 to 99min00sec, res. 10 sec
MAo
Maximum compressor ON time: 0.0 to 24h00min, res. 10 min
dn1
Delay don is enabled also for the first activation: n; Y
dF1
Delay doF is enabled also for the first deactivation: n; Y
roC
Compressor rotation function enabled (valid if oA2=CP2): n; Y
15.8 VENTILATOR MANAGEMENT
FPb
Regulation probe for ventilators: nP; P1; P2; P3; P4
Fon
Delay between two different ventilators start-up: 0 to 255 sec
FoF
Delay between two different ventilator switch-off: 0 to 255 sec
FSS
Maximum ventilator speed when Silent function is enabled: (0 to 100%;
nu=function disabled) Maximum speed for electronic or phase-cut controlled
ventilators.
roF
Ventilator rotation function enabled: n; Y
15.9 PHASE-CUT VENTILATOR CONTROL (OUTPUT OA3)
EFS
Ventilator speed (in percentage) in case of regulation probe (FPb) error: 0 to
100%
tP0
Output at maximum (100%) after start-up: 0 to 255 sec