EasyManuals Logo
Home>Emerson>Controller>Dixell XC15CX

Emerson Dixell XC15CX User Manual

Emerson Dixell XC15CX
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
1592001530 XC15-35CX EN r1.2 11.04.2017 XC15-35CX 34/40
17.3 “BUMP” FUNCTION
This feature is available only using ON-OFF compressors and if par. bMp=Y. When regulation
starts, the compressor will be activated and deactivated for a nub number of cycles and with a
duration respectively set in par. bon and boF. During the "BUMP" phase pressure/temperature
alarms are ignored.
17.4 COMPRESSOR CAPACITY LIMITATION IN CASE OF HIGH
CONDENSER PRESSURE/TEMPERATURE
If pressure/temperature measured from probe FPb>HAF, then the compressor capacity will be
able to be limited in the following way:
- By using par. HFL (if Digital or inverter-controlled compressor) for dHF interval of
time. After that, the compressor will be stopped if the alarm condition persists and if
HFC=YES
- Immediately stopped after dHF interval of time if ON-OFF compressor.
17.5 PRESSURE PROBE ERROR MANAGEMENT AT START-UP
At powering on, a pressure error probe will be signaled after the P1d delay expires. If pressure
error probe persists, the ON-OFF compressor will be activated following par. Con and CoF.
If regulation is stopped because of:
- Safety delays
- External alarms (from digital input)
- Pressure alarms
then any measured pressure value out of the probe range will not raise any additional alarm but
the display will show the last valid measured value.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Dixell XC15CX and is the answer not in the manual?

Emerson Dixell XC15CX Specifications

General IconGeneral
BrandEmerson
ModelDixell XC15CX
CategoryController
LanguageEnglish

Related product manuals