EMS 5000 FIREPOINT
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
6
1. How To Reset Fire & Fault Events.
To reset fires/faults on the 5000 FirePoint, insert the Key into the Panel’s Control Key
switch, located at the right of the Panel. Turn the Key to the “ON” Position.
Step Action Screen Display
No
1 This a normal Fire Event
2 Press the SILENCE ALARMS” button and the
screen will now briefly display: (Press Any
Key). Having silenced the System’s Sounders
and Internal Buzzers, an intermittent beep
every 10 – 15 seconds will occur until reset.
3 Press the “RESET/LED TEST” button and the
screen will now briefly display: (Press Any
Key)
4 The Event is now clear, so the key switch can
be returned to the “OFF” position. The screen
will now display:
01 FIRE ALARM TOT 01
RADIO CALLPOINT
ZONE 01
DEVICE 005
Alarms Silenced
Push Any Key
Device RESET:
RADIO CALLPOINT
Push Any Key
Status Normal