EMS 5000 FIREPOINT
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
14
7. How To Re-instate a Disabled Device Across a Network
To re-instate a Disabled a device across the network on the 5000 FirePoint, insert the
key into the Panels Control Key switch, located at the right of the panel.
Step Action Screen Display
No
1
With the key in the “ON” position, the screen
will display:
2
Press the “0” key and the screen will now
display:
3
Press the “∇” key until the screen displays:
4 Press the “YES” key and the screen will now
display:
5
Press the “∇” key until the screen displays:
6
Press the “YES” key and the screen will now
display:
NOTE: PAN is for a Hardwired based System. (Go to step 7).
NET is for a Radio LAN based system. (Go to step 8).
7
Press the “YES” key to select the required panel
type and the Screen will now display:
8
Press the “∇” key until the screen will display:
(Where Panel type = NET/PAN)
9
Press the “YES” key to change the panel
number until the required panel number is
shown: (e.g. 04)
10
Press the “∇” key until the screen displays:
Panel in Access
|***Options **** |
>Passwords <
| Time and Date |
| Logging |
>Fire System Opts <
| Remote Access |
Yes = select Time
|
** Fire system ** |
>Dev. Disable/Test <
| Net. Disable/Test |
Yes= Select Time
| Dev. Disable/Test |
>Net. Disable /Test <
| Det Zone Dis/Test |
Yes= Select Time
|* Network Status * |
>Panel Type : PAN <
| Panel : 00 |
Yes= Select Time
|* Network Status * |
> Panel Type:
NET<
| Panel : 00 |
Yes= Select Time
| Panel Type : NET |
>Panel : 00 <
| Device : 00 |
Yes= Select Time
| Panel Type : NET |
>Panel : 04 <
| Device : 00 |
Yes= Select Time
|Panel : 04 |
>Device : 00 <
|Status :Disable |
Yes= Select Time