EMS 5000 FIREPOINT
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
30
15. How To Test Individual Sounders
To test individual sounders on the 5000 FirePoint, Insert the key into the Panels Control
Key switch, Located at the right of the panel.
Step Action Screen Display
No
1
W
ith the key in the “ON” position, the screen
will display:
2 Press the “0” key and the screen will now
display:
3 Press the “∇” key until the screen displays:
4 Press the “YES” key and the screen will now
display:
5
Press the “∇” key until the screen displays:
6 Press the “YES” key and the screen will now
display:
7 Press 221100 then press the “YES” key
and the screen will display:
8
Press the “∇” key once and the screen will
display:
9
Press the “YES” key twice and the screen will
now display: (the first press of Yes enters you
into the sounder options menu the second
press of Yes does a configure stop)
10
Press the “∇” key until the screen displays
:
11
Press the “YES” key and the screen will now
display:
Panel in Access
|***Options **** |
>Passwords <
| Time and Date |
| Logging |
> Fire System Opts <
| Remote Access |
Yes = select Time
|** Fire system ** |
> Dev. Disable/Test <
| Net. Disable/Test |
Yes= Select Time
| System Mode |
> Engineers Config <
| Printer Options |
Yes= Select Time
Enter Your PIN
For Access>
Then Press YES
Time
|** Eng.; Config ** |
> Device Database <
| Sounder Options |
Yes= Select Time
| Sounder Config |
> Configure STOP <
| Configure START |
Yes= Select Time
| Configure START |
>Configure ONE <
| ^^^^^^^^^^^^^^^ |
Yes= Select Time
|** Configure ** |
>Sounder : ALLCFGD<
|Action : EVAC |
Yes= Select Time
|
Device Database |
>Sounder Options <
| Log On Devices |
Yes= Select Time