EMS 5000 FIREPOINT
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
25
12. How To Take Detector Zones Out Of Test
To take zones out of test and back into original state i.e. all on the 5000 FirePoint, insert
the key into the Panels Control Key switch, located at the right of the Panel. Turn the
key to the “ON” Position.
Step Action Screen Display
No
1 With the key in the “ON” position, the screen
will display:
2
Press the “0” key and the screen will now
display:
3
Press the “∇” key until the screen
displays:
4
Press the “YES” key and the screen will now
display:
5 Press the “∇” key until the screen displays:
6 Press the “YES” key and the screen will now
display:
7
Press the “∇” key once and the screen will now
display:
8
Press the “YES” key twice and the screen will
display: (This puts the status back to ACTIVE)
9
Press the “∆” key once and the screen will now
display:
10
Press the “YES” key and the screen will now
display:
|***Options **** |
> Passwords <
| Time and Date |
Panel in Access
|** Fire system ** |
> Dev. Disable /Test<
| Net. Disable /Test |
Yes= Select Time
| Net. Disable /Test |
>Det Zone. Dis /Test <
| Brigade Isolate |
Yes= Select Time
| ** Zone Status ** |
> Zone is: 01 <
| Status : Test |
Yes= Select Time
| Logging |
>Fire System Opts <
| Remote Access |
Yes= Select Time
| Z
> Status : Test <
| ^^^^^^^^^^^^^^^^|
Yes= Select Time
> Status : ACTIVE<
| ^^^^^^^^^^^^^^^^|
Yes= Select Time
| ** Zone Status ** |
> Zone is: 01 <
| Status : ACTIVE |
Yes= Select Time
| ** Zone Status ** |
> Zone is: 02 <
| Status : Test |
Yes= Select Time